Mr. Bernard P. Orlan March 20, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291 Real-Time Environmental Measurements
ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) in the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings began at 10:36 A.M. and concluded after 4:55 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 66.3 °F to 77.4 °F. Four (4) of the indoor measurements for temperature were below and twenty-nine (29) were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature ranged from 43.8 to 45.8 "F.
Relative Humidity
The relative humidity indoors ranged from 26.9 percent to 47.3 percent. Twenty-four (24) of the indoor measurements for relative humidity were below and sixty-four (64) are within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 27.3 to 47.4 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 449 ppm to 1293 ppm. Two (2) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 483 ppm. Therefore, the maximum acceptable level of CQ2 at this location was 1183 ppm (background level + 700 ppm). The highest reading (1293 ppm) was measured in room 705 approximately at 11:02 AM with 31 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were between 0 to 3 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from; 3 to 4 ppm.
Respirable Particulates CPM2,5)
Respirable particulate concentrations* indoors ranged between 3 pg/m^ to 37 pg/m^ with an average 11 pg/m^- All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. None of the eight-eight (88) instantaneous indoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 27 pg/rn- to 86 pg/m^ with an average of 59 pg/m^. Five (5) of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter.
CONFIDENTIAL, CITY_21MC100_003462077 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259138
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000259086
ATC indoor air quality report for the High School of Economics and Finance, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179985
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 21, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259315
ATC summary of IAQ measurements conducted May 2, 2002 at 100 Trinity Place.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000219855
Cover letter and summary report detailing indoor air quality measurements conducted at the High School of Economics and Finance.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259141
Indoor air quality measurements collected on March 20, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402529
Indoor air quality report for HS Economics & Finance, March 20, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396411
IAQ measurements performed at a NYC high school; report for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259300
IAQ measurements collected May 1, 2002 for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000254302
Indoor air quality measurements at H.S. Economics & Finance (M833) facility, March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259038
Indoor air quality measurements conducted March 7, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260018
IAQ measurements collected Mar 18, 2002 for BOE
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260023
IAQ measurements collected Mar 19, 2002 for BOE
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000259086
ATC indoor air quality report for the High School of Economics and Finance, March 2002.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179985
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 21, 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259937
IAQ measurements collected Mar 8, 2002 for BOE
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260018
IAQ measurements collected Mar 18, 2002 for BOE
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259141
Indoor air quality measurements collected on March 20, 2002 for BOE.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402529
Indoor air quality report for HS Economics & Finance, March 20, 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
ATC indoor air quality report for the High School of Economics and Finance, March 2002.
Similar indexed content
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 21, 2002.
Similar indexed content
ATC summary of IAQ measurements conducted May 2, 2002 at 100 Trinity Place.
Similar indexed content
NYC-WTC_000219855
Cover letter and summary report detailing indoor air quality measurements conducted at the High School of Economics and Finance.
Similar indexed content
Indoor air quality measurements collected on March 20, 2002 for BOE.
Similar indexed content