IAQ report, High School of Economics and Finance, Mar 2002

Machine-extracted title · confidence 32%

Indoor air quality measurements collected on March 20, 2002 for BOE.

NYC-WTC_000259141–000259144
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 21, 2002 Indoor Air Quality' Assessment Page 3 H.S. of Economics and Finance (M833)________ ArCPrpiectNpJ6-1912S0291 Real-Time Environmental Measurements

ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) in the school building and twelve (12) outdoors. Field data sheets are found in the Altachment. Readings began at 8:07 A.M. and concluded after 3:43 P.M. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 60.7 °F to 76.4 °F. Four (4) of the indoor measurements for temperature were above, twenty-three (23) were below, and sixty-one (61) were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating sea,son (wintertime conditions). The outdoor temperature ranged from 42.8 to 46.8 °F.

Relative Humidity

The relative humidity indoors ranged from 30.6 percent to 49.8 percent. All of the indoor measurements for relative humidity are within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 51.1 to 54.1 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 398 ppm to 1402 ppm. One (1) of the indoor measurements for CO2 was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 467 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1167 ppm (background level + 700 ppm). The highest reading (1402 ppm) was measured m 4th floor staircase A at approximately at 9:28 AM with 28 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were between 1 to 3 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 2 to 4 ppm.

Respirable Particulates (PM2 5)

Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 38 pg/m^ with ar average 5 pg/m^- All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. All of the eighty-eight (88) instantaneous indoor readings were below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 11 pg/m^ to 38 pg/m^ with an average of 25 pg/m3. All of the outdoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children.

CONFIDENTIAL, CITY_21MC100_003462093 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259143

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259143Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →