NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 14, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291 Real-Time ErmRONMENTAL Measurements

ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) in the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings began at 8:05 A.M. and concluded after 2:49 P.M. The results are described below.

Temneralure

Indoor dry bulb temperature measurements ranged from 62.9 °F to 76.7 °F. Three (3) of the indoor measurements were above and seventeen (17) were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature ranged from 43.1 to 46.2 °F.

Relative Humidity

The relative humidity indoors ranged from 30.4 percent to 71.6 percent. Three (3) of the indoor measurements for relative humidity were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 43.1 to 65.1 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 425 ppm to 1251 ppm. Two (2) of the indoor measurements for CO2 were above the ASHRAE Standard 6E-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 468 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1168 ppm (background level + 700 ppm). The highest reading (1251 ppm) was measured in the Cafeteria approximately at 1:36 PM with 2 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

QirbonMonoxideConcentratim

Carbon monoxide concentrations indoors were between 0 to 3 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 1 to 6 ppm.

Respirable Particulates (PM2j)

Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 40 pg/m^ with an average 7 pg/m^- All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. None of the eight-eight (88) instantaneous indoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 23 pg/m^ to 62 pg/m^ with an average of 33 pg/m^. None of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Three (3) instantaneous outdoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children.

C:iTY_21MC100_000467912 NYC-WTC_000384224

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000384224Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000259141

Indoor air quality measurements collected on March 20, 2002 for BOE.

Similar indexed content

Compare copies and versions →