NYC-WTC_000402510
Report of IAQ measurements collected March 18, 2002 at the HS building.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗Indoor air quality measurements collected for the HS of Economics & Finance; BOE involvement.
NYC-WTC_000384222–000384225OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 14, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291 Real-Time ErmRONMENTAL Measurements
ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) in the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings began at 8:05 A.M. and concluded after 2:49 P.M. The results are described below.
Temneralure
Indoor dry bulb temperature measurements ranged from 62.9 °F to 76.7 °F. Three (3) of the indoor measurements were above and seventeen (17) were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature ranged from 43.1 to 46.2 °F.
Relative Humidity
The relative humidity indoors ranged from 30.4 percent to 71.6 percent. Three (3) of the indoor measurements for relative humidity were above the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 43.1 to 65.1 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 425 ppm to 1251 ppm. Two (2) of the indoor measurements for CO2 were above the ASHRAE Standard 6E-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 468 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1168 ppm (background level + 700 ppm). The highest reading (1251 ppm) was measured in the Cafeteria approximately at 1:36 PM with 2 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
QirbonMonoxideConcentratim
Carbon monoxide concentrations indoors were between 0 to 3 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 1 to 6 ppm.
Respirable Particulates (PM2j)
Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 40 pg/m^ with an average 7 pg/m^- All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. None of the eight-eight (88) instantaneous indoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 23 pg/m^ to 62 pg/m^ with an average of 33 pg/m^. None of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Three (3) instantaneous outdoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children.
C:iTY_21MC100_000467912 NYC-WTC_000384224
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000402510
Report of IAQ measurements collected March 18, 2002 at the HS building.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000254302
Indoor air quality measurements at H.S. Economics & Finance (M833) facility, March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259141
Indoor air quality measurements collected on March 20, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259038
Indoor air quality measurements conducted March 7, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402529
Indoor air quality report for HS Economics & Finance, March 20, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296812
ATC IAQ measurements report for 90 Trinity Place, Apr 22, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259180
IAQ measurements collected April 11, 2002 for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000219855
Cover letter and summary report detailing indoor air quality measurements conducted at the High School of Economics and Finance.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259315
ATC summary of IAQ measurements conducted May 2, 2002 at 100 Trinity Place.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259136
Indoor air quality measurements report for the High School of Economics and Finance, March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396411
IAQ measurements performed at a NYC high school; report for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179972
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 8, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000402510
Report of IAQ measurements collected March 18, 2002 at the HS building.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259141
Indoor air quality measurements collected on March 20, 2002 for BOE.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259038
Indoor air quality measurements conducted March 7, 2002 at the referenced school.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296812
ATC IAQ measurements report for 90 Trinity Place, Apr 22, 2002.
Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402529
Indoor air quality report for HS Economics & Finance, March 20, 2002.
Similarity score 0.992 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260120
ATC IAQ measurements collected April 22, 2002 at the referenced school, BOE program.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000402510
Report of IAQ measurements collected March 18, 2002 at the HS building.
Similar indexed content
NYC-WTC_000254302
Indoor air quality measurements at H.S. Economics & Finance (M833) facility, March 2002.
Similar indexed content
Indoor air quality measurements collected on March 20, 2002 for BOE.
Similar indexed content
NYC-WTC_000259038
Indoor air quality measurements conducted March 7, 2002 at the referenced school.
Similar indexed content
NYC-WTC_000402529
Indoor air quality report for HS Economics & Finance, March 20, 2002.
Similar indexed content