Indoor air quality report, HS for Leadership & [name], Apr

Machine-extracted title · confidence 28%

ATC IAQ measurements report for 90 Trinity Place, Apr 22, 2002.

NYC-WTC_000296812–000296815
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 23, 2002 Indoor Air Quality Assessment Pages H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 Real-Time Environmental Measurements ATC collected one hundred and nineteen (119) sets of real-time environmental measurements consisting of one hundred and thirteen (113) in the school building and six (6) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began in the morning and concluded in the afternoon. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 52.3 °F to 85.7°F. Twenty two (22) of the indoor measurements were bellow and fifty seven (57) measurements were above, and thirty four (34) measurements are within range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature range was 72.4 °F to 83.9 °F.

RelatiyeHumidity

The relative humidity indoors ranged from 33.2 percent to 58.2 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 332.9 to 36.7 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 102 ppm to 1047 ppm. All of the indoor measurements for CO2 were below the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 822 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1522 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 0 ppm.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 42 pg/m^ with an average 11 pg/m^- All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m3 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and one (1) measurement was above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 12 pg/m^ to 16 pg/m^ with an average of 14 ug/'mA All of the outdoor measurements for PM2,5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter, and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CITY_21MC100_003086711

NYC-WTC_000296814

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000296814Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000394809

Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.

Similar indexed content

NYC-WTC_000260159

April 2002 IAQ measurement summary for the referenced high school.

Similar indexed content

NYC-WTC_000399204

IAQ measurements at the High School for Leadership & [name] provided to NYC BOE; May 2002.

Similar indexed content

NYC-WTC_000370501

Indoor air quality measurements collected March 14, 2002 at the referenced school.

Similar indexed content

Compare copies and versions →