NYC-WTC_000259038
Indoor air quality measurements conducted March 7, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗Indoor air quality measurements at H.S. Economics & Finance (M833) facility, March 2002.
NYC-WTC_000254302–000254305OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan March 8, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291 Real-Time Environmental Measurements
ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) in the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings began at 8:07 A.M. and concluded after 6:37 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 65.1 °F to 79.2 °F. Nine (9) of the indoor measurements were below and forty-two (42) were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature ranged from 53.4 to 59 °F.
Relative Humidity
The relative humidity indoors ranged from 24.5 percent to 36.2 percent. Forty-four (44) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. Forty-four (44) measurements were within the ASHRAE recommended range. The outdoor relative humidity ranged from 23.3 to 30.1 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 402 ppm to 1420 ppm. Eighty-seven (87) of the indoor measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 684 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1384 ppm (background level + 700 ppm). The highest reading (1420 ppm) was measured in stairwell A 6^^ floor at 5:48 PM. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 1 to 4 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 2 to 4 ppm.
Respirable Particulates (PM2_s)
Respirable particulate concentrations* indoors ranged between 1 pg/m^ to 25 pg/m^ with an average 8 pg/m^- None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The indoor PM2.5 average concentration was also below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. The outdoor respirable particulate concentration ranged from 69 pg/m^ to 112 pg/m^ with an average of 89 pg/m^. All of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children.
CONFIDENTIAL, CITY_21MC100_003395225 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000254304
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000259038
Indoor air quality measurements conducted March 7, 2002 at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259141
Indoor air quality measurements collected on March 20, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384222
Indoor air quality measurements collected for the HS of Economics & Finance; BOE involvement.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402510
Report of IAQ measurements collected March 18, 2002 at the HS building.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000402529
Indoor air quality report for HS Economics & Finance, March 20, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296812
ATC IAQ measurements report for 90 Trinity Place, Apr 22, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259136
Indoor air quality measurements report for the High School of Economics and Finance, March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260159
April 2002 IAQ measurement summary for the referenced high school.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260120
ATC IAQ measurements collected April 22, 2002 at the referenced school, BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394809
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259086
ATC indoor air quality report for the High School of Economics and Finance, March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259995
IAQ measurements collected Mar 14, 2002 for BOE
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000259038
Indoor air quality measurements conducted March 7, 2002 at the referenced school.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259141
Indoor air quality measurements collected on March 20, 2002 for BOE.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260159
April 2002 IAQ measurement summary for the referenced high school.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239106
Letter from ATC Associates reporting indoor air quality measurements collected at J.H.S. 131M on August 22, 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384222
Indoor air quality measurements collected for the HS of Economics & Finance; BOE involvement.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000239434
Report on indoor air quality measurements conducted at a New York City high school on August 22, 2002.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000259038
Indoor air quality measurements conducted March 7, 2002 at the referenced school.
Similar indexed content
Indoor air quality measurements collected on March 20, 2002 for BOE.
Similar indexed content
NYC-WTC_000384222
Indoor air quality measurements collected for the HS of Economics & Finance; BOE involvement.
Similar indexed content
NYC-WTC_000402510
Report of IAQ measurements collected March 18, 2002 at the HS building.
Similar indexed content
NYC-WTC_000402529
Indoor air quality report for HS Economics & Finance, March 20, 2002.
Similar indexed content