Mr. Bernard P. Orlan March 14, 2002 Indoor Air Quality Assessment Page 4 H.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291 * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOCCon^tration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATION

During this assessment, ATC noted the following; • The interior of the building appeared clean and free of dust and debris; • The building was occupied al the time of the assessment; • No smoke odor was detected in the building;

FINDER

Based on the real-time measurements, the following findings are presented;

1. Concentrations of CO and TVOCs were below applicable standards and guidelines. 2. Three (3) of the indoor measurements for relative humidity were above the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 3. Three (3) of the indoor measurements for temperature were above and seventeen (17) were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 4. Two (2) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. 5. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/'m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.. Three (3) instantaneous outdoor readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or 212.

Sincerely, ATC ASSOCIATES n Revi

/ iannis Efstathiou, James R. Cohn, CIH, CSP Senior Project Manager Regional Manager, Industrial Hygiene Division

Attachment

CITY_21MC100_000467913 NYC-WTC_000384225

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000384225Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000259141

Indoor air quality measurements collected on March 20, 2002 for BOE.

Similar indexed content

Compare copies and versions →