Indoor air quality report, HS Economics & Finance, Apr 2002

Machine-extracted title · confidence 42%

IAQ measurements conducted April 11, 2002 for BOE at the referenced school.

NYC-WTC_000383080–000383083
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 12, 2002 Indoor Air Quality Assessment Page 4 H.S. of Economics and Finance (M833) ATC Project No. 15-19125-0291 * The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: 9 The interior of the building appeared clean and free of dust and debris; 9 The building was occupied at the time of the assessment; 9 No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO2,CO and TVOCs were below applicable standards and guidelines. 2. Eleven (11) of the indoor measurements for temperature were above, and seventy seven (77) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3. Seven (7) of the indoor measurements for relative humidity were below and eighty one (81) were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 4. None of the indoor measurements for PM 2.5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. None of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Four (4) of the twelve (12) instantaneous outdoor reading were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 211 or 212.

Sincerely, Reviewed by: A TC ASSOCIA TES INC. \ ___ Prasad Doddapaneni James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division Attachment:

CITY_21MC1OO_OO28798O8

NYC-WTC_000383083

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000383083Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →