NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Indoor air quality report, HS Economics & Finance, Apr 2002

Machine-extracted title · confidence 42%

IAQ measurements conducted April 11, 2002 for BOE at the referenced school.

NYC-WTC_000383080–000383083
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 12,2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291 Real-Time Environmental Measurements

ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) in the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings began atlO:53 A.M. and concluded after 17:57 P.M. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 70.5 °F to 76.5 °F. Eleven (11) of the indoor measurements for temperature were above, and seventy seven (77) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature ranged from 56.3 to 62.2 °F.

Relative Humidity

The relative humidity indoors ranged from 29.6 percent to 40.0 percent. Seven (7) of the indoor measurements for relative humidity were below and eighty one (81) were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 28.4 to 35.8 percent.

Carbon DioxideConcentrqtipn

Carbon dioxide concentrations indoors ranged from 476 ppm to 1104 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 614 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1314 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon MoripjddeCpncentrqtion

Carbon monoxide concentrations indoors were between 1 to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration ranged from 2 ppm to 4 ppm.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 2 pg/m^ to 13 pg/m^ with an average 5 pg/m^- None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 18 pg/m^ to 82 pg/m^ with an average of 36 pg/m^. None of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Four (4) of the twelve (12) instantaneous outdoor reading were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children.

CITY_21MC100_002879807

NYC-WTC_000383082

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000383082Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →