machine-extracted · confidence unavailable · Check page ↗Indoor Air Quality Report, March 21, 2002, NYC School
Machine-extracted title · confidence 98%Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 21, 2002.
NYC-WTC_000179985–000179989
OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
I Mr. Bernard P. Orlan March 22, 2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)________ ATC Project No. 15-19125-0291 Real-Time Environmental Measurements
ATC collected one hundred (100) sets of real-time environmental measurements consisting of eighty-eight (88) in the school building and twelve (12) outdoors. Field data sheets are found m the Attachment. Readings began at 8:03 A.M. and concluded after 2:51 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 64.8 °F to 75 °F. Fourteen (14) of the indoor measurements for temperature were below and seventy-four (74) were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature ranged from 46.5 to 63.1 °F.
Relative Humidity
The relative humidity indoors ranged from 26.7 percent to 41.9 percent. Forty-eight (48) of the indoor measurements for relative humidity are below and forty (40) were within the ASHRAF recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 26.1 to 33.4 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 339 ppm to 1442 ppm. Three (3) of the indoor measurements for CO2 were above the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 465 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1165 ppm (background level + 700 ppm). The highest reading (1442 ppm) was measured in the cafeteria at approximately at 1:29 PM with 160 occupants. Fevels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were between 1 to 3 ppm. These concentrations were below the NPAAQS/ASHRAF guideline of 9 ppm. The outdoor CO concentration ranged from 2 to 5 ppm.
Respirable Particulates (PMjj)
Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 53 pg/m^ with a:n average 12 pg/m^. All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. One (1) of the eighty-eight (88) instantaneous indoor readings was above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentration ranged from 37 pg/m^ to 74 pg/m^ with an average of 64 pg/m^. Seven (7) of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter.
CONFIDENTIAL, CITY_21MC100_003462108 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000179987
OCR can misread numbers and units. Confirm readings against the page image before using them.
Related records
Browse subjects →Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
Same-box records
NYC-WTC_000180183
Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗14 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179980
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.993
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000175231
Memo reporting indoor air quality measurements collected at DeSoto School on August 26, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗12 shared non-person entities · 1 shared topics · similarity 0.992
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000175150
Letter and report from ATC Associates regarding indoor air quality measurements collected at DeSoto School in August 2002.
12 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗12 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179972
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 8, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗11 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗12 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000177847
Cover letter and report detailing indoor air quality measurements collected at PS 234M on January 24, 2002, to evaluate building contamination.
12 shared non-person entities · 1 shared topics · similarity 0.991
machine-extracted · confidence unavailable · Check page ↗Filed elsewhere
No available related records indexed in this group.
More like this page
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Similarity score 0.991 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180183
Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in March 2002.
Similarity score 0.984 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179972
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 8, 2002.
Similarity score 0.982 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000175231
Memo reporting indoor air quality measurements collected at DeSoto School on August 26, 2002.
Similarity score 0.981 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Similarity score 0.980 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180188
Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in April 2002.
Similarity score 0.979 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Buildings in this record
Machine-extracted building matches; verify each source. Buildings, never households.
- 100 Trinity Place · 1 pages · confidence 0.15 · verify page 1
Others also read
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
Similar indexed content
Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in March 2002.
Similar indexed content
Similar indexed content
Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 14, 2002.
Similar indexed content
NYC-WTC_000175231
Memo reporting indoor air quality measurements collected at DeSoto School on August 26, 2002.
Similar indexed content