Indoor Air Quality Report, March 21, 2002, NYC School

Machine-extracted title · confidence 98%

Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 21, 2002.

NYC-WTC_000179985–000179989
Page image
Scanned page image, NYC-WTC_000179988
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 22, 2002 Indoor Air Quality Assessment Page 4 H.S. of Economics and Finance fM833) ATC Project No. 15-19125-0291 Eleven (11) of the twelve (12) outdoor instantaneous readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building;

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of respirable particulates, CO and TVOCs were below applicable standards and guidelines. 2. Fourteen (14) of the indoor measurements for temperature were below and seventy-four (74) were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 3. Forty-eight (48) of the indoor measurements for relative humidity are below and forty (40) were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. 4. Three (3) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The highest reading (1442 ppm) was measured in the cafeteria at approximately at 1:29 PM with 160 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary' source of CO2 indoors is occupant respiration. 5. All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. One (1) of the eighty-eight (88) instantaneous indoor readings was above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. Seven (7) of the outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Eleven (11) of the twelve (12) outdoor instantaneous readings were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children.

CONFIDENTIAL, CITY_21MC100_003462109 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000179988

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000179988Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000180183

Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in March 2002.

Similar indexed content

NYC-WTC_000179980

Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 14, 2002.

Similar indexed content

Compare copies and versions →