Mr. Bernard P. Orlan March 11, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290 Real-Timie En\ ironmental Measurements ATC collected one: hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 10:40 A.M. and concluded after 3:50 P.M. The results are described below'.

Tempera^r^

Indoor dry bulb temperature measurements ranged from 66.0 °F to 72.7 °F. Eight (8) indoor measurement were below and One Hundred Twenty (120) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 48.0 °F to 62.8 °F.

Relative Humiditv

The relative humidity indoors ranged from 33.0 percent to 48.1 percent. All One hundred and twenty eight (128) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 33.4 to 49.7 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 462 ppm to 963 ppm. All of the measurements were below' the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 470 ppm. Therefore, the maximum acceptable level of CO? at this location W'as 1170 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. Tlie primary' source of COy indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 1 ppm 3 ppm. These concentrations were below the NP?iAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 3ppm-5 ppm.

Respirable Particulates (PM2,s)

Respirable particulate concentrations* indoors ranged between 33pg/m3 to 61 pg/nP with an average 44 pg/m^- None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. One hundred and ten (110) of the one hundred and twenty eight (128) instantaneous measurements w’ere above the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^. The outdoor respirable particulate concentrations ranged from 119 pg/m^ to 164 pg/m^ with an average of 130 pg/m^. All twelve (12) outdoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. All of the outdoor

CONFIDENTIAL, CITY_21MC100_003463588 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000259939

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000259939Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000370492

Indoor air quality measurements collected March 12, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000259995

IAQ measurements collected Mar 14, 2002 for BOE

Similar indexed content

NYC-WTC_000260023

IAQ measurements collected Mar 19, 2002 for BOE

Similar indexed content

NYC-WTC_000370501

Indoor air quality measurements collected March 14, 2002 at the referenced school.

Similar indexed content

Compare copies and versions →