Mr. Bernard P. Orlan March 28, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership <& Public Service (M894) ATC Proiect No. 15-19125-0290 REAtATiME Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourieen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 8:01 A.M. and concluded after 3:21 P.M. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 73.2 °F to 78.8 °F. One hundred and seventeen (117) indoor measurements for temperature were above and eleven (11) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 59.4 °F to 62.4 °F.
Relative Humidity
The relative humidity indoors ranged from 28.4 percent to 38.3 percent. Fifty (50) of the indoor measurements for relative humidity were below and seventy-eight (78) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 27.2 to 35.7 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 467 ppm to 781 ppm. All of the indoor measurements for COg were below the ASHRAE Standard 62-1999 recommended maximum concentration of <:700 ppm above the background level. The outdoor (background) CO2 concentration w'as 486 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1186 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide ooncentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NP.\AQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 3 ppm- 4 ppm.
Respirable Particulates (PM2_5)
Respirable particulate concentrations* indoors ranged between 2 pg/m^ to 33 pg/m^ with an average 5 pg/m^- All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 27 pg/m^ to 89 pg/m^ with an average of 59 pg/m^. Five (5) of the outdoor measurements for PM2.5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Nine (9) of
CONFIDENTIAL, CITY_21MC100_003463820 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000260062
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000260018
IAQ measurements collected Mar 18, 2002 for BOE
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260023
IAQ measurements collected Mar 19, 2002 for BOE
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000409958
ATC report of IAQ measurements at High School for Leadership, March 2002, for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259932
IAQ measurements collected Mar 7, 2002 for BOE
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259941
IAQ measurements collected Mar 11, 2002 for BOE
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000180183
Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260028
ATC report of IAQ measurements at High School for Leadership & [name], 90 Trinity Place, requested by NYC BOE in March 2002.
13 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370496
Indoor air quality measurements collected March 13, 2002 at the referenced school.
12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000370505
Indoor air quality measurements collected March 15, 2002 at the referenced school.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259937
IAQ measurements collected Mar 8, 2002 for BOE
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259086
ATC indoor air quality report for the High School of Economics and Finance, March 2002.
11 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260065
ATC IAQ report for 90 Trinity Place school, measurements collected April 8, 2002, BOE program.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000259937
IAQ measurements collected Mar 8, 2002 for BOE
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259086
ATC indoor air quality report for the High School of Economics and Finance, March 2002.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260018
IAQ measurements collected Mar 18, 2002 for BOE
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000260023
IAQ measurements collected Mar 19, 2002 for BOE
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259136
Indoor air quality measurements report for the High School of Economics and Finance, March 2002.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259932
IAQ measurements collected Mar 7, 2002 for BOE
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
IAQ measurements collected Mar 18, 2002 for BOE
Similar indexed content
IAQ measurements collected Mar 19, 2002 for BOE
Similar indexed content
NYC-WTC_000409958
ATC report of IAQ measurements at High School for Leadership, March 2002, for BOE.
Similar indexed content
IAQ measurements collected Mar 7, 2002 for BOE
Similar indexed content
IAQ measurements collected Mar 11, 2002 for BOE
Similar indexed content