NYC 9/11 Public Portal Document
Mr Bernard P Orlan March 14 2002
Indoor Air Quality Assessment Page 4
H S for Leadership & Public Service fM894) ATCProiectNo 15 19125 0290
above and one (1) was below the USEPA recommended concentration for sensitive individuals
such as asthmatic people and children of 40 pg/m^
* The measurements made durmg this assessment were instantaneous readings the NPAAQS is
a 24 hour average
Type Concentration
The TVOCs concentrations were 0 ppm mside the building These concentrations were below
the AJHA guideline for odor control of 1 ppm The outdoor TVOC concentration was also 0
ppm
OBSERVATIONS
During this assessment ATC noted the following
• The interior of the building appeared clean and free of dust and debris
• The building was occupied at the time of the assessment
• No smoke odor was detected in the building
FINDINGS
Based on the real time measurements the following findings are presented
1 Concentrations of CO and TVOCs were below applicable standards and guidelines
2 Seventeen (17) indoor measurement for temperature were withm and one hundred eleven
(111) measurements were above the range of 68 to 75°F (at 50 percent relative humidity)
recommended by ASHRAE Standard 55 1992 dunng the heating season (wintertime
conditions)
3 All of the indoor measurements for relative humidity were within the ASHRAE
recommended range of 30 to 60 percent for occupant comfort
4 All but one of the indoor measurements for CO2 were below the ASHRAE Standard 62 1999
recommended maximum concentration of <700 ppm above the background level The
highest reading (1289 ppm) was measured in room 1005 at 10 59 AM with 31 occupants
Levels above the recommended maximum do not indicate a health risk Carbon dioxide
measurements are used as an indicator of available outdoor air The primary source of CO2
indoors is occupant respiration
5 All of the indoor measurements were below the NPAAQS of 65 pg/m^ 24 hour average
concentration of particulate matter 2 5 micrometers or less in aerodynamic diameter One (1)
of the one hundred twenty eight (128) instantaneous indoor readings was above the USEPA
recommended concentration for sensitive individuals such as asthmatic people and children
of 40 pg/m^ Three (3) outdoor measurements were above the NPAAQS of 65 pg/m^ 24
hour average concentration of particulate matter 2 5 micrometers or less in aerodynamic
diameter Eleven (11) of the outdoor instantaneous measurements were above and one (1)
was below the USEPA recommended concentration for sensitive individuals such as
asthmatic people and children of 40 pg/m^
CITY_21MC100_003085433