Machine-extracted title · confidence 50%

ATC report of IAQ measurements at NYC school; March 11, 2002.

NYC-WTC_000295811–000295815
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr Bernard P Orlan March 12 2002 Indoor Air Quality Assessment Page 4 H S for Leadership & Public Service (MS94~) ATCProiectNo 15 19125 0290 micrometers or less in aerodynamic diameter All of the outdoor instantaneous measurements were above the USEPA recommended concentration for sensitive mdividuals such as asthmatic people and children of 40 pg/m^

* The measurements made durmg this assessment were instantaneous readings the NPAAQS is a 24 hour average

T7OC Concentration

The TVOCs concentrations were 0 ppm inside the building These concentrations were below the AJHA guideline for odor control of 1 ppm The outdoor TVOC concentration was also 0 ppm

OBSERVATIONS

During this assessment ATC noted the following • The interior of the building appeared clean and free of dust and debns • The building was occupied at the time of the assessment • No smoke odor was detected in the building

FINDINGS

Based on the real time measurements the following findmgs are presented

1 Concentrations of CO and TVOCs were below applicable standards and guidelines 2 Five (5) indoor temperature measurement were below five (5) measurements were above and one hundred eighteen (118) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55 1992 during the heating season (wintertime conditions) 3 One hundred and twenty three (123) indoor measurements for relative humidity were below and five (5) measurements were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort 4 One hundred twenty six (126) indoor measurements for CO2 were below and two (2) were above the ASHRAE Standard 62 1999 recommended maximum concentration of <700 ppm above the background level The outdoor (background) CO2 concentration was 724 ppm Therefore the maximum acceptable level of CO2 at this location was 1424 ppm (background level + 700 ppm) The highest indoor measurements was taken m room 506 at 12 19 PM with 27 occupants Levels above the recommended maximum do not indicate a health risk Carbon dioxide measurements are used as an indicator of available outdoor air The primary source of CO2 indoors is occupant respiration 5 None of the indoor measurements for respirable particulates were above the NPAAQS of 65 pg/m^ 24 hour averageconcentration of particulate matter 2 5 micrometers or less m aerodynamic diameter and the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^

CITY_21MC100_003085394

NYC-WTC_000295814

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000295814Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →