March 2002 IAQ measurements at selected NYCBOE school for QA purposes.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗March 27, 2002 IAQ measurements at School for Leadership & [name], NYC BOE.
NYC-WTC_000295928–000295932OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr Bernard P Orlan March 28 2002 Indoor Air Quality Assessment Page 4 H S for Leadership & Public Service (M894) ATCProiectNo 15 19125 0290 the twelve (12) instantaneous outdoor measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children
* The measurements made during this assessment were instantaneous readings the NPAAQS is a 24 hour average
TVOC Concentration
The TVOCs concentrations were 0 ppm mside the building These concentrations were below the AIHA guideline for odor control of 1 ppm The outdoor TVOC concentration was also 0 ppm
OBSERVATIONS
During this assessment ATC noted the following • The interior of the building appeared clean and free of dust and debris • The building was occupied at the time of the assessment • No smoke odor was detected in the building
FINDINGS
Based on the real time measurements the following findings are presented
1 Concentrations of CO2 CO and TVOCs were below applicable standards and guidelines 2 One hundred and seventeen (117) indoor measurements for temperature were above and eleven (11) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55 1992 dunng the heatmg season (wintertime conditions) 3 Fifty (50) of the indoor measurements for relative humidity were below and seventy eight (78) measurements were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort 4 All of the indoor measurements for PM2 5 were below the NPAAQS of 65 pg/m^ 24 hour average concentration of particulate matter 2 5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children Five (5) of the outdoor measurements for PM2 5 were above the NPAAQS of 65 pg/m^ 24 hour average concentration of particulate matter 2 5 micrometers or less in aerodynamic diameter Nine (9) of the twelve (12) instantaneous outdoor measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children
CITY_21MC100_0 03085630
NYC-WTC_000295931
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000295890
March 2002 IAQ measurements at selected NYCBOE school for QA purposes.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295885
March 2002 IAQ measurements at NYC Board of Education school as part of QA program.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295787
ATC report detailing IAQ measurements at NYC school; March 7, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295811
ATC report of IAQ measurements at NYC school; March 11, 2002.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295895
March 2002 IAQ measurements at a NYCBOE school to assess air quality maintenance.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295923
March 26, 2002 IAQ measurements at School for Leadership & [name], NYC BOE.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295792
ATC report on IAQ measurements conducted at the referenced NYC school.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295915
March 22, 2002 IAQ measurements at School for Leadership & [name], NYC BOE.
12 shared non-person entities · 1 shared topics · similarity 0.996
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295866
ATC report on indoor air quality measurements at NYC school; March 14, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295919
March 25, 2002 IAQ measurements at School for Leadership & [name], NYC BOE.
12 shared non-person entities · 1 shared topics · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295745
ATC memo about IAQ measurements at a NYC school for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295768
ATC report of IAQ measurements at a NYC school for BOE.
13 shared non-person entities · 1 shared topics · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000295890
March 2002 IAQ measurements at selected NYCBOE school for QA purposes.
Similarity score 0.998 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295885
March 2002 IAQ measurements at NYC Board of Education school as part of QA program.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295787
ATC report detailing IAQ measurements at NYC school; March 7, 2002.
Similarity score 0.997 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295846
ATC report on indoor air quality at a NYC school; March 13, 2002.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000295792
ATC report on IAQ measurements conducted at the referenced NYC school.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000211863
Letter and report from ATC Associates detailing indoor air quality measurements collected at the school on March 27, 2002, to evaluate possible contamination.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000295890
March 2002 IAQ measurements at selected NYCBOE school for QA purposes.
Similar indexed content
NYC-WTC_000295885
March 2002 IAQ measurements at NYC Board of Education school as part of QA program.
Similar indexed content
NYC-WTC_000295787
ATC report detailing IAQ measurements at NYC school; March 7, 2002.
Similar indexed content
NYC-WTC_000295811
ATC report of IAQ measurements at NYC school; March 11, 2002.
Similar indexed content
NYC-WTC_000295895
March 2002 IAQ measurements at a NYCBOE school to assess air quality maintenance.
Similar indexed content