Indoor air quality report, BOE school

Machine-extracted title · confidence 41%

March 2002 IAQ measurements at a NYCBOE school to assess air quality maintenance.

NYC-WTC_000295895–000295899
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr Bernard P Orlan March 21 2002 Indoor Air Quality Assessment Page 4 H S for Leadership & Public Service CM 894) ATCProiectNo 15 19125 0290 particulate matter 2 5 micrometers or less m aerodynamic diameter One (1) of the twelve (12) instantaneous outdoor readings was above the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^

* The measurements made during this assessment were mstantaneous readings the NPAAQS is a 24 hour average

TVOC Concentration

The TVOCs concentrations were 0 ppm inside the buildmg These concentrations were below the AIHA guideline for odor control of 1 ppm The outdoor TVOC concentration was also 0 ppm

OBSERVATIONS

During this assessment ATC noted the following • The interior of the building appeared clean and free of dust and debns • The building was occupied at the time of the assessment • No smoke odor was detected in the building

FINDINGS

Based on the real time measurements the following findings are presented

1 Concentrations of CO and TVOCs were below applicable standards and guidelines 2 Seventy five (75) indoor measurement for temperature were above and fifty three (53) measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55 1992 dunng the heating season (wintertime conditions) 3 Three (3) of the indoor measurements for relative humidity were below and one hundred twenty five(125) were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort 4 One of the mdoor measurements for CO2 was above the ASHRAE Standard 62 1999 recommended maximum concentration of <700 ppm above the background level The highest reading (1364 ppm) was measured in room 506 at 12 48 PM with 34 occupants Levels above the recommended maximum do not indicate a health risk Carbon dioxide measurements are used as an indicator of available outdoor air The pnmary source of CO2 indoors is occupant respiration 5 All of the indoor measurements for PM2 5 were below the NPAAQS of 65 pg/m^ 24 hour average concentration of particulate matter 2 5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^ All of the outdoor measurements were below the NPAAQS of 65 pg/m3 24 hour average concentration of particulate matter 2 5 micrometers or less in aerodynamic diameter One (1) of the twelve (12) mstantaneous outdoor readings was above the USEPA recommended concentration for sensitive individuals such as asthmatic people and children of 40 pg/m^

CITY_21MC100_003085532

NYC-WTC_000295898

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000295898Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →