operational for the first two months of the project. Eventual repair of the elevator by others
allowed access to the inner compartment. The elevator cab and the exterior top of the cab were
vacuumed.
2.G.4. Basement (Study)
The basement of the building is comprised of separate rooms: a trash compactor room, a motor
room associated with the elevator shaft, a common access area from the street, and a fire
protection equipment room. The brick walls of the basement were crusted with mud, indicating a
high water level at some time in the building's history. These rooms were cleaned using the
commercial HEPA equipment. Loose debris related to stone and mortar deterioration was
vacuumed from the walls and ledges of the base of the elevator shaft. Small rocks, paper, debris,
and rodent carcasses were removed.
2.H. Cleaning of Non-Study Commercial Units
Commercial Units Lemongrass Grill, Food Exchange and Barber Shop; below-grade common
areas; and two condensers on the roof were also cleaned. These areas were cleaned using
cleaning methods as presented in Attachment 12, Synopsis of Cleaning Methods by Building
Area. The condensers on the atrium roof were cleaned with a HEPA-filtered vacuum.
The sequence of procedures for vacuuming, wet wiping, waste management, and pre-cleaning
and post-cleaning sampling mirrored the procedures used in the residential units. Management of
waste was accomplished as the cleaning activities occurred. Disposal of debris was handled in
the same manner as in the residential units. Cleaning of the HVAC systems presented the only
significant difference from the cleaning procedures used in the residential units. A discussion of
the types of HVAC systems contained in these commercial units and the procedures used to clean
these HVAC systems follows.
Commercial Lemongrass Grill, occupies 2,351 square feet of space. A self-contained
re-circulating HVAC system with no outdoor supply air is suspended above the floor in the South
end of the restaurant. Return air enters the unit through a grill located in the front side of the unit.
The air-handling unit is accessible through access doors on either side of the unit. The unit is
enclosed in one-half inch of sheet rock. A supply trunk runs northward through the restaurant
with three supply branches. A second source of duct is located adjacent to an exhaust hood for
the cooking equipment. This system is separate from the HVAC and supplies makeup air to the
hood area. Ambient air is drawn in from a grill above street level to a blower inside the building
that leads to a supply trunk. Four supply grills are adjacent to the food exhaust hood.
Commercial Unit Food Exchange is a restaurant that occupies 2,324 square feet of space, running
from Cedar Street at the South end through to Liberty Street on the North end. Two side-by-side
air handlers that share the supply air duct system are supported above a decorative tinned
acoustical ceiling. The supply duct system splits mid building and runs approximately fifty feet in
two opposite directions. A water cooling tower is located outside the building on the building
21