Maintain the cleaning zone under negative pressure using a HEPA filtered air filtration device
whenever possible.
11.3 Site-specific Cleaning Procedures
11.3.1 Lemon Grass Restaurant
This is a 2,351 sq ft space with variable ceiling height. One air handling unit is located above the
ceiling toward the south end of the floor. This is a recirculating air unit with no outdoor air
supply. Return air enters the unit through a grille located in the side of the unit. The air handling
unit is accessible and is provided with access doors. The air handling unit distributes supply air
through a main supply air duct and several branch ducts. Supply air diffuser openings are
located on the underside of the supply duct (most of the diffusers have been removed). The
supply diffuser openings extend in a line to the north of the air handling units and are spaced
approximately 15’ apart. There are approximately four 18” supply diffuser openings located to
the north of the air handling unit. There is a separate ducted make-up air system that delivers
outdoor air to the cooking stations. The make-up air system consists of a single duct with
diffuser openings on the underside of the duct, and a blower assembly that is located in-line with
the duct. Outdoor air is provided to the make-up air system through a ducted outdoor air intake
located in an exterior wall of the building approximately 10’ above ground level.
VENTILATION SYSTEM COMPONENTS TO BE CLEANED
The following system components will be cleaned in the Lemon Grass Restaurant:
a. Air handling unit and components
b. Reheat Coil
c. Supply air ducts and terminal difiusers
d. Makeup Air System
e. Dissembled Duct Sections on Floor
CLEANING PROCEDURES
General: Any interior surfaces of the air handling unit or ventilation system that are porous shall
be cleaned using manual HEPA vacuuming methods. After successful completion of visual
inspection and verification sampling, a lockdown encapsulant shall be applied to the porous
surfaces using a hand-operated sprayer or brush, using care not to coat electrical or mechanical
components.
Note that if any dissembly of the air handling units is required to complete the work, the air
handling unit shall be reassembled by a qualified HVAC professional after all parts are dry and
are verified clean.
Note that all HEPA air filtration devices and HEPA-filtered vacuum collection devices shall be
exhausted to the outdoors.