IAQ report, Stuyvesant High School, Dec 2001

Machine-extracted title · confidence 66%

Indoor air quality measurements collected on December 20, 2001 at Stuyvesant High School.

NYC-WTC_000255594–000255597
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Tempera/.iire

Indoor dry bulb temperature measurements ranged from 70,0 °F to 76.1 °F.- Five (5) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHR.AE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected on the 41'1, 5*-'^ and 6^11 floors. The outdoor temperature range was 44.9 to 48.8 °F.

Relalive Humidity

The relative humidity indoors ranged from 17.9 percent to 44.0 percent. Ninety-nine (99) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 30.4 and 58.0 percent.

Cai'hon Dioxide Conreritration

Carbon dioxide concentrations indoors ranged from 509 ppm to 1338 ppm. Two (2) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 459 ppm and 462 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1162 ppm (background level -H 700 ppm). The highest reading, 1338 ppm, was in Room 403. Rooms with CO2 levels above the recommended maximum were found on 4^^* and floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Coucenlration

Carbon monoxide concentrations indoors were 1-3 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 1-4 ppm.

Respirable Particulates (PM2,p)

Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 32 pg/m^. All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 7 and 53 pg/m^.

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3'''^, 4th, 6^11 and 7^*1 floors (See Attachment 1). The PM2.5 concentration range for those rooms was 9-32 pg/m^ with an average of approximately 17 pg/m^. The PM2.5 concentration range for the other rooms was 6-27 pg/m^ with an average of approximately 12 pg/nP. The average PM2.5 concentration for the entire school building was approximately 13 pg/mA In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 9-25 pg/m^ with an average of approximately 16 pg/np.

CONFIDENTIAL, CITY_21MC100_003457277 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000255596

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000255596Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000255838

IAQ measurements conducted January 14, 2002 for Stuyvesant High School.

Similar indexed content

NYC-WTC_000273956

Internal memo accompanying IAQ measurements at Stuyvesant High School and BOE notice.

Similar indexed content

Compare copies and versions →