IAQ report, Stuyvesant High School, Dec 2001

Machine-extracted title · confidence 66%

Indoor air quality measurements collected on December 20, 2001 at Stuyvesant High School.

NYC-WTC_000255594–000255597
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.

EVALUATION CMTERIA

Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:

yentilaiioii for Acceptable door Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide io Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).

Table I lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.

TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED

si‘-- PARAMETER TARGET LEVEL rt. OR^A^ON . Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable' 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (p.g/m3) 24-hour average Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at50%RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile I ppm Organic Compounds AI HA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AI HA = American Industrial Hygiene Association

Real-Time Environmental Measurements

ATC collected one hundred and twenty-seven (127) sets of real-time environmental measurements consisting of one hundred and twenty-five (125) in the school building and two (2) outdoors. All ten floors of the school were surx'eyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 8:05 A.M. and concluded after 4:00 P.M.

CONFIDENTIAL, CITY_21MC1OO_OO3457276 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000255595

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000255595Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000255838

IAQ measurements conducted January 14, 2002 for Stuyvesant High School.

Similar indexed content

NYC-WTC_000273956

Internal memo accompanying IAQ measurements at Stuyvesant High School and BOE notice.

Similar indexed content

Compare copies and versions →