Indoor air quality measurements collected December 11, 2001 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗Indoor air quality measurements collected on December 13, 2001 at the referenced school.
NYC-WTC_000255543–000255546OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. ■ For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications;
Ventilation for Acceptable Indoor Air.Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation; Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
Carbon Dioxide <700 parts per million (ppm) I ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ■ ASHRAE 62 (adopted from (CO) USEPA NPAAQS) . Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average Temperature Summer: 73-79U- at 50% RH ASHRAE55 Winter: 68-75°F at 50% RH Relative Humidity 30-60% ASHRAE 55 Total Volatile 1 ppm Organic Compounds AIHA (TVOC)' USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AtHA - American Industrial Hygiene Association
Real-Time Environmental Measurements
ATC collected one hundred and twenty-seven (127) sets of real-time environmental measurements consisting of one hundred and twenty-five (125) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 8:10 A.M. and concluded after 3:40 P.M. <
CONFIDENTIAL, CITY_21MC1OO_OO3457181 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000255544
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000401467
Indoor air quality measurements collected December 11, 2001 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255518
IAQ measurements reported for Stuyvesant High School; December 10, 2001.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255522
Indoor air quality measurements at Stuyvesant High School, December 12, 2001.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401450
Indoor air quality measurements conducted December 10, 2001 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273995
December 2001 IAQ measurements at Stuyvesant High School with BOE contact.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401502
Indoor air quality measurements collected December 13, 2001 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401484
Indoor air quality measurements collected December 12, 2001 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255564
Indoor air quality measurements collected on December 17, 2001 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274016
December 2001 IAQ measurements at Stuyvesant High School with BOE references.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255539
ATC IAQ report of measurements collected December 12, 2001, at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401506
Indoor air quality measurements collected December 17, 2001 at Stuyvesant High School.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274012
December 2001 IAQ measurements at Stuyvesant High School with BOE references.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000401819
ATC indoor air quality report dated January 16, 2002 for Stuyvesant High.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255518
IAQ measurements reported for Stuyvesant High School; December 10, 2001.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000274016
December 2001 IAQ measurements at Stuyvesant High School with BOE references.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000273956
Internal memo accompanying IAQ measurements at Stuyvesant High School and BOE notice.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000401484
Indoor air quality measurements collected December 12, 2001 at Stuyvesant High School.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000255564
Indoor air quality measurements collected on December 17, 2001 at Stuyvesant High School.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000401467
Indoor air quality measurements collected December 11, 2001 at Stuyvesant High School.
Similar indexed content
IAQ measurements reported for Stuyvesant High School; December 10, 2001.
Similar indexed content
NYC-WTC_000255522
Indoor air quality measurements at Stuyvesant High School, December 12, 2001.
Similar indexed content
Indoor air quality measurements conducted December 10, 2001 at Stuyvesant High School.
Similar indexed content
December 2001 IAQ measurements at Stuyvesant High School with BOE contact.
Similar indexed content