IAQ report, Stuyvesant HS, Dec 2001

Machine-extracted title · confidence 66%

Indoor air quality measurements collected on December 17, 2001 at Stuyvesant High School.

NYC-WTC_000255564–000255567
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information ' presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.

EVALUATION CRITERIA

Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:

Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-J999f American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human OccupancyfASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations' (1993), American Industrial Hygiene Association (AIHA).

Table 1 lists target guidelines for the parameters that ATG evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.

TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED

iPARAMETERUf,,- agency OR , .. ' ORGANIZATION Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE- 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms, per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average Temperature Summer: 73-79°F at 50% KH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile 1 ppm Organic Compounds AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association

Real-Time Environmental Measurements

ATC collected one hundred and twenty-seven (127) sets of real-time environmental measurements consisting of one hundred and twenty-five (125) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below. Field data sheets are found in Attachment 1. Readings began at 8:00 A.M. and concluded after 3:45 P.M.

CONFIDENTIAL, CITY_21MC100_003457219 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000255565

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000255565Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000274012

December 2001 IAQ measurements at Stuyvesant High School with BOE references.

Similar indexed content

NYC-WTC_000255518

IAQ measurements reported for Stuyvesant High School; December 10, 2001.

Similar indexed content

NYC-WTC_000274016

December 2001 IAQ measurements at Stuyvesant High School with BOE references.

Similar indexed content

Compare copies and versions →