IAQ report, Stuyvesant HS, Dec 2001

Machine-extracted title · confidence 66%

Indoor air quality measurements collected on December 17, 2001 at Stuyvesant High School.

NYC-WTC_000255564–000255567
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Temperature

Indoor dry bulb temperature measurements ranged from 69.0 °F to 78.3 °F. Eleven (11) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 50.0 to 55.0 °F. .

' Relative Humidity

The relative humidity . indoors ranged from 20.5 percent to 32.4 percent. Eight (8) measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. , All other measurements were below the recommended range. The outdoor relative humidity range was 26.3 and 30.5 percent.

CarionDioxideConcentratiop

Carbon dioxide concentrations indoors ranged from 555 ppm to 1785 ppm. Eight (8) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <7.00 ppm above the background level. The outdoor (background) CO2 concentrations were 528 ppm and 540 ppm. Therefore, the maximum acceptable level of COg at this location was 1240 ppm (background level + 700 ppm). The highest reading, 1785 ppm, was in Room 717. Rooms with CO2 levels above the recommended maximum were found on 3rd, 4th, 5fl'> and 7th floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air' Tire primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0-3 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 2 ppm.

Respirable Particulates (PM2 §)

Respirable particulate concentrations* indoors ranged between 14 pg/m^ to 34 pg/m^. All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 38 and 54 pg/m^.

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 6^*'' and 7^^ floors (See Attachment 1). The PM2 5 concentration range for those rooms was 14-32 pg/m^ with an average of approximately 22 pg/m-. The PM2.5 concentration range for the other rooms was 14-34 pg/m^ with an average of approximately 21 pg/m3. The average P]^2.5 concentration for the entire school building was approximately 21 pg/m^. In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 12-25 pg/m^ with an average of approximately 20 pg/m3.

CONFIDENTIAL, CITY_21MC100_003457220 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000255566

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000255566Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000274012

December 2001 IAQ measurements at Stuyvesant High School with BOE references.

Similar indexed content

NYC-WTC_000255518

IAQ measurements reported for Stuyvesant High School; December 10, 2001.

Similar indexed content

NYC-WTC_000274016

December 2001 IAQ measurements at Stuyvesant High School with BOE references.

Similar indexed content

Compare copies and versions →