NYC 9/11 Public Portal Document

Temperature

Indoor dry bulb temperature measurements ranged from 70.0. °F to 79.4 °F. Sixty-six (66) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 48..8 to 59.6 °F.

Jielative Humidit}/

The relative humidity indoors ranged from 24.1 percent to 33.8 percent. One hundred and two (102) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. Tlie outdoor relative humidity range was 27.2 and 34.3 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 510 ppm to 1923 ppm. Seven (7) CO2 measurements ' were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 493 ppm and 506 ppm.' Therefore, the maximum acceptable level of CO2 at this location was 1206 ppm (background level + 700 ppm). The highest reading, 1923 ppm, was in Room 735. Rooms with CO2 levels above the recommended maximum were found on 3'’^^, 4tl'' and 7^^ floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0-1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. Tire outdoor CO concentration was Ippm.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 26 pg/m^ to 63 pg/m^. All measurements were within the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 58 and 60 pg/m^.

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3rd, 4th, (jth and 7th floors (See Attachment 1). The PM2.5 concentration range for those rooms was 27 - 41 pg/m3 with an average of approximately 35 pg/mA The PM2 5 concentration range for the other rooms was 26 - 63 pg/m^ with an average of approximately 36 pg/m^. The average PM2.5 concentration for the entire school building was approximately 36 pg/m^. In addition to higher efficiency rating filters on their IlVAC units, portable High Efficiency. Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 24 - 34 pg/m^ with an average of approximately 28 pg/m^.

CONFIDENTIAL, CITY_21MC100_003457163 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000255541

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000255541Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000255518

IAQ measurements reported for Stuyvesant High School; December 10, 2001.

Similar indexed content

NYC-WTC_000273973

Memorandum regarding indoor air quality measurements at Stuyvesant High School.

Similar indexed content

Compare copies and versions →