IAQ report, Stuyvesant HS, Dec 12 2001

Machine-extracted title · confidence 41%

Indoor air quality measurements collected December 12, 2001 at Stuyvesant High School.

NYC-WTC_000401484–000401487
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Temperature

Indoor dry bulb temperature measurements ranged from 70.0. °F to 79.4 °F. Sixty-six (66) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 48..8 to 59.6 °F. ,

Relative Humidity .

Tlie relative humidity indoors ranged from 24.1 percent to 33.8 percent. One hundred and two (102) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 27.2 and 34.3 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 510 ppm to 1923 ppm. Seven (7) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 493 ppm and 506 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1206 ppm (background level + 700 ppm). The highest reading, 1923 ppm, was I in Room 735. Rooms with CO2 levels above the recommended maximum were found on 3’’^, 4^11 and 7th floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors.were 0-1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was Ippm.

Respirable Particulates (PM2, s)

Respirable particulate concentrations* indoors ranged between 26 pg/m^ to 63 ug/mT All measurements were within the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 58 and 60 pg/m^.

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3''‘^, 4th, 6th and 7th floors (See Attachment 1). The PM2.5 concentration range for those rooms was 27-41 pg/m3 with an average of approximately 35 pg/m^. The PM2.5 concentration range for the other rooms was 26 - 63 pg/nP with an average of approximately 36 pg/m^. The average PM2.5 concentration for the entire school building was approximately 36 pg/m^. In addition to higher efficiency rating filters on their HVAC units, portable. High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 24 - 34 pg/m^ with an average of approximately 28 pg/m^.

CITY_21MC100_002897338

NYC-WTC_000401486

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000401486Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000273973

Memorandum regarding indoor air quality measurements at Stuyvesant High School.

Similar indexed content

NYC-WTC_000274012

December 2001 IAQ measurements at Stuyvesant High School with BOE references.

Similar indexed content

NYC-WTC_000401450

Indoor air quality measurements conducted December 10, 2001 at Stuyvesant High School.

Similar indexed content

Compare copies and versions →