Temperature

Indoor di-y bulb temperature measurements ranged from 71.5 °F to 78.6 °F. Eighty-four (84) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 54.6 to 59.9 °F.' " ‘ .

Relative Humidity

The relative humidity indoors ranged from 34.0 percent to 51.9 percent. All measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 46.0 and 54.5 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 580 ppm to 1921 ppm. Twelve (12) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. Tire outdoor (background) CO2 concentrations were 528 ppm and 535 ppm. Tlterefore, the rnaximum acceptable level of CO2 at this location was ppm (background level -1- 700 ppm). The highest reading, 1921 ppm, was in Room 717. Rooms with CO2 levels above the recommended maximum were found on pt, 3rd, 4th, 5th and 7th floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 1-3 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 2 ppm-

Respirable Particulates (PM2,5J

Respirable particulate concentrations* indoors ranged between 41 pg/m^ to 116 pg/ra^. Ninety­ seven (97) measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 100 and 105 pg/m^.

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3rd^ 4th, gth amj 7th floors (See Attachment 1). The PM2.5 concentration range for those rooms was 42 - 76 pg/m^ with an average of approximately 64 pg/m^. The PM2.5 concentration range for the other rooms was 41 - 110 pg/m^ with an average of approximately 73 pg/m^. The average PM2.5 concentration for the entire school building was approximately 36 pg/m^. In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2,5 concentration range for these rooms was 42 - 60 pg/m^ with an average of approximately 54 pg/m^.

CONFIDENTIAL, CITY_21MC1OO_OO3457182 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000255545

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000255545Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000255518

IAQ measurements reported for Stuyvesant High School; December 10, 2001.

Similar indexed content

NYC-WTC_000401450

Indoor air quality measurements conducted December 10, 2001 at Stuyvesant High School.

Similar indexed content

NYC-WTC_000273995

December 2001 IAQ measurements at Stuyvesant High School with BOE contact.

Similar indexed content

Compare copies and versions →