Temperature

Indoor diy bulb temperature measurements ranged from 71.6 °F to 80.2 °F. Eighty-six (86) measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected throughout the school building. The outdoor temperature range was 53.6 to 57.8 °F.

Relative Humidity

The relative humidity indoors ranged from 24.5 percent to 33.4 percent. Ninety-one (91) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 29.3 and 39.5 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 542 ppm to 1363 ppm. Six (6) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 -concentrations were 492 ppm and 499 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1199 ppm (background level + 700 ppm). The highest reading, 1949 ppm, was in Room 505. Rooms with CO2 levels above the recommended maximum were found on 3''^, 4th and 5th floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0-2 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0- Ippm.

Respirable Particulates (PM2,3)

Respirable particulate concentrations* indoors ranged between 13 pg/m^ to 50 pg/m^. All measurements were within the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 35 and 49 pg/m^.

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3'’^, 4th, 6’1’ and 7th floors (See Attachment 1). The PM2 5 concentration range for those rooms was 16-31 pg/mJ with an average of 21 pg/m^. The PM2.5 concentration range for the otlier rooms was 13-50 pg/m^ with an average of approximately 25 pg/m^. The average PM2.5 concentration for the entire school building was approximately 24 pg/m^. [n addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 15-28 pg/m^ with an average of approximately 20 pg/in3.

CITY_21MC100_002897319

NYC-WTC_000401469

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000401469Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000273973

Memorandum regarding indoor air quality measurements at Stuyvesant High School.

Similar indexed content

NYC-WTC_000274012

December 2001 IAQ measurements at Stuyvesant High School with BOE references.

Similar indexed content

Compare copies and versions →