NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Indoor air quality report, Stuyvesant HS, Jan 2002

Machine-extracted title · confidence 42%

ATC report of indoor air quality measurements at Stuyvesant High School (M477).

NYC-WTC_000311194–000311197
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

TciJipei'ciiurL'

Indoor dry bulb temperature measurements ranged from 66.8 °F to 74.4 °F. Two (2) measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected on the 4th, 5th and 6th floors. The outdoor temperature range was 36.7 to 42.1 °F.

Re/alive Hiimic/i!v

The relative humidity indoors ranged from 13.0 percent to 29.3 percent. All measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 16.5 and 19.9 percent.

Carbon Dioxide Concenlrtiiron

Carbon dioxide concentrations indoors ranged from 470 ppm to 1450 ppm. Nine (9) CO? measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COo concentrations were 459 ppm and 478 ppm. Therefore, the maximum acceptable level of CO? at this location was 1 178 ppm (background level + 700 ppm). The highest reading, 1450 ppm, was in Room 327. Rooms with CO? levels above the recommended maximum were found on 4^1 and 7^1 floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concenlralion

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was I ppm.

Re.',/iirah/e Pariiciilaies (PMj jJ

Respirable particulate concentrations* indoors ranged between 5 pg/iiN to 20 pg/nP. All measurements were below the NPAAQS of 65 pg/nP 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 20 and 25 pg/nP.

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3''d, 4^1, and 7^1 floors (See Attachment 1). The PM? j concentration range for those rooms was 5 - 20 (.Lg/m^ with an average of approximately 10 pg/m^. The PM? 5 concentration range for the other rooms was 6-19 pg/mJ with an average of approximately 9 pg/nN, The average PM2.5 concentration for the entire school building was approximately 9 pg/m^. In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM? 5 concentration range for these rooms was 5-25 pg/nN with an average of approximately 14 pg/m^.

CITY_21MC100_003044888

NYC-WTC_000311196

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000311196Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000401739

Indoor air quality report for Stuyvesant High School, January 2002.

Similar indexed content

Compare copies and versions →