Indoor air quality report, Stuyvesant HS, Jan 2002

Machine-extracted title · confidence 42%

ATC report on indoor air quality measurements at Stuyvesant High School (M477).

NYC-WTC_000311190–000311193
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Teiiiperaliire

Indoor dry bulb temperature measurements ranged from 67.6 °F to 74.6 °F. Two (2) measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected on the 4^iT and 6'''’ floors. The outdoor temperature range was 34.8 to 44.5 °F.

Re/alive Humiclily

The relative humidity indoors ranged from 1 1.9 percent to 23.5 percent. All measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 13.3 and 14.6 percent.

Carbon Dioxide CoiiceiUradon

Carbon dioxide concentrations indoors ranged from 510 ppm to 1530 ppm. Four (4) CO2 measurements were above the ASHR.AE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO? concentrations were 460 ppm and 487 ppm. Therefore, the maximum acceptable level of CO2 at this location was I 187 ppm (background level + 700 ppm). The highest reading, 1530 ppm, was in Room 505. Rooms with CO2 levels above the recommended maximum were found on 4th , 5th, 6th and 7th floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also I ppm.

Res/drub/e Parliciilutes

Respirable particulate concentrations* indoors ranged between 5 pg/m-’ to 19 pg/m^. All measurements were below the NPA.AQS of 65 pg/m-’ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were I 5 and 30 pg/m-’.

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3rd, 4th, (3th 7th floors (See Attachment 1). The PMo 5 concentration range for those rooms was 5-16 pg/mJ with an average of approximately 1 1 pg/m-’. The PM2.5 concentration range for the other rooms was 7-19 pg/m-’ with an average of approximately 12 pg/m-*. The average PMo 5 concentration for the entire school biiildingwas appro,ximately 12 pg/mA In addition to higher efficiency rating filers on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327. 333. 638 and 740. The PRb 5 concentration range for these rooms w as 9 - 19 pg/nP w ith an average of approximately 14 pg/nP.

CITY_21MC100_003044880

NYC-WTC_000311192

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000311192Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000274045

December 20, 2001 IAQ measurements at Stuyvesant High School for BOE.

Similar indexed content

Compare copies and versions →