ATC memo, Stuyvesant HS IAQ, Jan 2002

Machine-extracted title · confidence 42%

ATC memo detailing IAQ measurements at Stuyvesant High School.

NYC-WTC_000255777–000255780
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

>

Tciiipcrcitiire

Indoor dry bulb temperature measurements ranged from 66.8 °F to 74.4 °F. Two (2) measurements were below the range of 68' to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected on the 4d\ 5^'' and bdi floors. The outdoor temperature range was 36.7 to 42.1 °F.

Re/uliyeHumidity

The relative humidity indoors ranged from 13.0 percent to 29.3 percent. All measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 16.5 and 19.9 percent.

Ccirhon Dioxide Conceiilralion

Carbon dioxide concentrations indoors ranged from 470 ppm to 1450 ppm. Nine (9) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO? concentrations were 459 ppm and 478 ppm. Therefore, the maximum acceptable level of COc at this location was 1178 ppm (background level + 700 ppm). The highest reading, 1450 ppm, was ill Room 327. Rooms with CO? levels above the recommended maximum were found on 4th and 7*'’ floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO? indoors is occupant respiration.

Carbon Monoxide Cunccniralion

.Carbon monoxide concentrations indoors, were 0 ppm for all readings.- These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO, concentration was I ppm.

Respircib/e Dcirlicii/uies (PM?^

Respirable particulate concentrations* indoors ranged between 5 pg/mJ to 20 pg/mJ. All measurements were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 20 and 25 pg/mJ. • , . '

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3rd, 4th, gth and 7^^ floors (See Attachment 1). The PM? 5 concentration range for those rooms was 5 - 20 pg^P with an average of approximately 10 pg/m^. The PM?.5 concentration range for the other rooms was 6 - 19 pg/m^ with an average of approximately 9 pg/m-’. The average PM? 5 concentration for the entire school building was approximately 9 pg/m^. In addition to higher efficiency rating Alters on their HVAC units, portable High Efficiency Particulate Air ■(HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2,5 concentration range for these rooms was 5 - 25 pg/m-’ with an average of approximately 14 pg/m-’.

CONFIDENTIAL, CITY_21MC100_003457518 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000255779

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000255779Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →