Indoor air quality report, Stuyvesant HS, Jan 2002

Machine-extracted title · confidence 39%

ATC IAQ measurements report for Stuyvesant High School dated January 2, 2002.

NYC-WTC_000401735–000401738
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Teniperciiiire

Indoor dry bulb temperature measurements ranged from 67.6 °F to 74.6 °F. Two (2) measurements were below the range of 68 to 75°F- (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). These measurements were collected on the 41l'>, 5111 and bth floors. The outdoor temperature range was 34.8 to 44.5 °F.

Relutive Hwnidily

The relative humidity indoors ranged from I 1.9 percent to 23.5 percent: All measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 13.3 and 14,6 percent.

Ccirhon Dioxide Concenirciimn

Carbon dioxide concentrations indoors ranged from 510 ppm to 1530 ppm. Four (4) CO? measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) COg concentrations were 460 ppm and 487 ppm. Therefore, the maximum acceptable level of CO? at this location was 1 187 ppm (background level + 700 ppm). The highest reading, 1530 ppm, was in-Room 505. Rooms with COg levels above the recommended maximum were found on 4tl‘i , 5^l\ and 7^''' floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO? indoors is occupant respiration.

Carbon Monoxide ConcenUxition

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm.' The outdoor CO concentration was . also Ippm.

Respirable Parliciilulex fRM2^

Respirable particulate concentrations* indoors ranged between 5 pg/nP to 19 pg/m^. All measurements were below the NPAAQS of .65 pg/nP .24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 15 and 30 pg/nP.

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3''*^', 4^11, 6^11 and 7^1'' floors (See Attachment 1). The PMg.s concentration range for those rooms was 5-16 pg/m-^ with an average of approximately 1 1 pg/mJ. The PM? 5 concentration range for the other rooms was 7 - 19 pg/m-’ with an average of approximately 12 pg/nP. The average PMo 5 concentration for the entire school building was approximately 12 pg/nP. In addition to higher efficiency rating filters on their HVAC units, portable High Efficiencv’ Particulate Air (HEPA) purifiers were placed in Rooms 327.-333, 638 and 740. The PMg 5 concentration range for these rooms was 9 - 19 pg/nP with an average of approximately 14 pg/nP.

CITY_21MC100_002897686

NYC-WTC_000401737

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000401737Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000401739

Indoor air quality report for Stuyvesant High School, January 2002.

Similar indexed content

Compare copies and versions →