* The measurements made during this assessment were instantaneous readings, theNPAAQS is a 24-hour average.

TVOC Concentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • Windows were open in Room 738; • The HEPA air purifier in room 638 was turned off.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of respirable particulates, CO and TVOCs were within applicable standards and guidelines.

2. Two (2) CO2 measurements were above the range recommended by ASHRAE 62-1999. All ' others were below the recommended maximum concentration.

3. Five (5) temperature measurements were above the range recommended by ASHRAE 55- 1992.

4. Ninety-nine (99) measurements of relative humidity were below the ASHRAE- recommended range of 30 to 60 percent for occupant comfort.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 26101-212.

Sincerely, A TC ASSOCIA TES INC. Reviewed by:

Andreas C. Andreou James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division

Attachment

CONFIDENTIAL, CITY_21MC100_003457278 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000255597

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000255597Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000255838

IAQ measurements conducted January 14, 2002 for Stuyvesant High School.

Similar indexed content

NYC-WTC_000273956

Internal memo accompanying IAQ measurements at Stuyvesant High School and BOE notice.

Similar indexed content

Compare copies and versions →