Temperatur-e

Indoor dry bulb temperature measurements ranged from 69.3 °F to 76.5 °F. Only one (.1) measurement was above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). This measurement was collected from room 638. The outdoor temperature range was 48.1 to 49.7 °F.

Relative Humidity

The relative humidity indoors ranged from 27.0 percent to 44.3 percent. Fourty-eight (48) measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 48.3 and 49.0 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 585 ppm to 1605 ppm. Six (6) CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 545 and 595 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1295 ppm (background level -1- 700 ppm). The highest reading, 1605 ppm, was in Room 735. Rooms with CO2 levels above the recommended maximum were found on 3'’^, 4^^, 5^1'' and 71^ floors. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 - t ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0-3 ppm.

Respirable Particulates (PM2,

Respirable particulate concentrations* indoors ranged between 16 pg/m^ to 71 pg/nP. Three (3) measurements were. above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 79 and 83 pg/m^.

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3rd, 4th, gth ainj 7th floors (See Attachment 1). The PM2.5 concentration range forthose rooms was 16-68 pg/m^ with an average of approximately 43 pg/m^. The PM2.5 concentration range for the other rooms was 16-71 pg/nP with an average of approximately 43 pg/m^. The average PM2,5 concentration for the entire school building was approximately 43 pg/mA In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 30 - 55 pg/m^ with an average of approximately 41 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CITY_21MC1OO_OO2897796

NYC-WTC_000401821

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000401821Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000255838

IAQ measurements conducted January 14, 2002 for Stuyvesant High School.

Similar indexed content

NYC-WTC_000255855

ATC memo/IAQ measurements reported for Stuyvesant High School.

Similar indexed content

NYC-WTC_000227030

Report letter from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School in January 2002.

Similar indexed content

Compare copies and versions →