TVOC Coiwentration

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The interior of the building appeared clean and free of dust and debris; • The building was occupied at the time of the assessment; • No smoke odor was detected in the building; • The portable HEPA air purifier in rooms 333, 638 and 740 were turned off; • One of the windows in room 638 was opened.

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO and TVOCs were within applicable standards and guidelines.

2. Six (6) CO2 measurements were above the range recommended by ASHRAE 62-1999. All others were below the recommended maximum concentration.

3. Fourty-eight (48) indoor measurements of relative humidity were below the ASHRAE- recommended range of 30 to 60 percent for occupant comfort.

4. Only one (1) temperature measurement was above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).

5. Three (3) respirable particulate measurements were above the NPAAQS of 65 pg/m^ 24- hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 261 or 212.

Sincerely, A TC ASSOCIA TES INC. Reviewed by:

Andreas C. Andreou James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division Attachment

CITY_21MC100_002897797

NYC-WTC_000401822

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000401822Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000255838

IAQ measurements conducted January 14, 2002 for Stuyvesant High School.

Similar indexed content

NYC-WTC_000255855

ATC memo/IAQ measurements reported for Stuyvesant High School.

Similar indexed content

NYC-WTC_000227030

Report letter from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School in January 2002.

Similar indexed content

Compare copies and versions →