MAYOR’S OFFICE OF EMERGENCY MANAGEMENT
SUPPLEMENT TO THE HVAC SPECIFICATION
SECTION 15120
1. Paragraph 1.1.A.5 - Delete “and the discharge plenum at the emergency generators.”
Add the following;
Discharge plenum at the emergency generators shall be double wall construction 4" thick,
built of 16 GA galvanizes sheet metal with high temperature block insulation.
Plenum shall be built as per SMACNA standards for 2" w.g. pressure classification. All
joints, seams, connections and abutments to the building structure shall be sealed with
suitable pressure and temperature compounds and gaskets.
Pipe penetrations shall be sealed to prevent air leakage and condensation movement
through the seal. Inner sheet shall be of G90 coated galvanized steel with welded
connections. All weld on casing interior shall be painted.
Plenum shall be constructed to withstand 133% of the rated pressure without structure
failure. Wall and roof deflections at the rated pressure shall not exceed 1/8" per foot.
High temperature block insulation shall be 11 lbs. Per cu. ft. Density molded hydrous
calcium silicate with a maximum K factor of 0.42 at 200 degrees F mean temperature.
Insulation shall be securely wired in place with copper clad wire or galvanized steel
bands ('/2" x .015) on 12" centers.
All joints and voids of insulation shall be filled and pointed with mineral wool cement.
SECTION 15150
1. Add paragraph 1.1 .M
Dampers shown on drawings designated as “F/SM” shall comply with the following:
Dampers shall be pneumatically operated combination fire and smoke Ruskin, Imperial,
or approved equal. They shall be provided with factory installed U.L. rated full sleeves.
Provide air foil or “V” Blade damper blades supported with shafts and stainless steel
bearings to allow daily operation. Provide intermediate supports for damper blades more
than 36" long. They shall conform to UL Standard 555S as leakage rated dampers in
smoke control systems and when closed shall be the equivalent of a 1-1/2 hour fire
damper. Leakage shall conform to Class 2 withjnaximum leakage of lOCFM/Sq. Ft. at