PROJECT memorandum
TO; M/. ;.M«jh.SHCA SUBJECT; 0EM-7WTC
FROM: M . V. Lemeshev JOBNO-t 1854
CC: DATE: February 15,2000 ,
' 'o improve operating conditions of the fuel oil fill pump set ti’ansferring oil from tiie '
uildins storage tank to the tenant’s storage tank, a? it is based on the field observation
y the equipment manufaauxer’s represmtarive, v/e recommend to remove existing apti-
iphon valve and to install check valve.
?heok valve shall be installed as close as possible to the building's storage tank. Use
pring loaded check valve for horizontal application.
V. \im^U£SUS}<.0(riVUMO2liMUl llae
FEB 15 : 0BB 16’36 PAGE.02