NYC 9/11 Public Portal Document 18:31 FAX 2122190256 SWANKE HAYDEN CONNELL 07;04 FAX 212 615 3700 COSENTINI ASSOCIATES 0002

zSENTINI ASSOCIATES LLP ■ TWO PENN. PLAZA, NEW YORK, NY 10121 ■ 212-615-3600 ■ FAX 212-615-3700

JOB MEMORANDUM

TO: Joe Alrotta SUBJECT: [email protected].

FROM: Ron Pincott JOB NO: 1854

CC: M. Maybaum J. Dwyer DATE: July 6,1999 V. Lemeshev

RE; 7th Floor Domestic Booster System Bearing Drips

We have reviewed the domestic water booster system located on the 7th floor with (he supplier of the system. The pump provided has bearings that are water cooled. This discharge is very limited in flow. To eliminate the problem of getting rid of this water, we propose (he use of an automatic pump and collection tank unit. This unit will be installed adjacent to the pump package and will sit on the waterproofed floor.

The pump unit shall be:

• Federal Pump Corporation model AITV automatic unit

• Heavy duty 10 gallon tank

• Pump; 1/3 h-p. 1750 RPM -Single phase 60 eye. 115 volt with cord and plug -20 GPM - 10 ft. hd. -2" inlet - 1" discharge

Provide 2" trap and funnel on tank inlet for proposed I.W. from bearing seals of domestic pump system. Connect pump discharge pipe to the existing sump pump discharge pipe at the corridor wall. Provide check valve and shutoff valve in discharge piping.

A 120V 30 amp receptacle shall be provided at die location of the new pump for plug in connection. This shall be coordinated with the electrical contractor.

We are reviewing the building alternate to the self contained plump and tank unit.

X:\WI»U’ILES\l854.99\Rl’CM0706.M01

JUL 07 ’99 18 ••47 2122190256 PAGE,02

NYC-WTC_000172160

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000172160Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Memo on Domestic Water Booster System, August 1999 · Box 7DCAS

NYC-WTC_000172580

Technical memo proposing installation of an automatic pump and collection tank to resolve water discharge issues from the domestic water booster system on the 7th floor.

1 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.950

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000172580 · Box 7DCAS

Technical memo proposing installation of an automatic pump and collection tank to resolve water discharge issues from the domestic water booster system on the 7th floor.

Similar indexed content

NYC-WTC_000171691 · Box 7DCAS

Technical proposal to install an automatic pump and collection unit for the domestic water booster system dated August 2, 1999.

Similar indexed content

Compare copies and versions →