5, Install emergency break glass stop button per contract drawing.
Remark; R.B. Samuels to install.
6. Con ect load bank on generator Remove jumper and install new components.
Remark; Ambassac^or to address.
1. Investigate why on initial generator start-up generator #3 stopped running due to air in the
fuel line.
Remark; Was this an isolated or re-occuning problem? H.O, Penn to investigate.
Conclusion. The emergency generator system was left in the automatic position and is
ready to deliver emergency power at demand. The items noted above
should be addressed as soon as possible for proper design operation.