PPS-Generators

Q. Site Tests

1. Manufacturer shall provide the services of factory trained engineer and the technicians to conduct and supervise the installation and site tests.

2. Generator set supplier shall supervise reinstallation of components, align, inspect and re-certify each unit after installation. Any deficiency with the installation shall be brought to the attention of the contractor for repair or alteration. The unit shall be started up and run at No Load to determine that all systems are functional.

3. To demonstrate satisfactory operation of the generator sets each shall be automatically started, paralleled and run with the load of the resistive load bank system. Test shall continue to demonstrate shutdown and load shed sequences. The owner and engineer shall witness this test. The test shall be run a minimum of two (2) hours with as much on-site load as is available. Test reports shall be filled in during the test to record, as a minimum, voluge, amperage, frequency, oil pressure, water temperature and ambient temperature at 15 minute intervals. These reports shall be provided to the owner and engineer after the test for his approval.

4. In addition to the above running test, there should a ftmctional test of any feature of the generator that may not have been installed properly or altered since the factory test. As an example, for the remote annunciator, each light on the panel should be tested to verify it works as installed. Submit a test plan to the engineer, prior to testing, which shows which tests are to be performed.

R. Operation and Maintenance Manuals

1. The bidder shall furnish six copies of operating and maintenance instructions and illustrated parts books covering the engine-generator and auxiliary equipment which will require operating instructions and periodic maintenance.

S. Commissioning

1. Furnish the services of a competent, factory-trained engineer or technician to be available at the job site for period of two days for initial start-up and for instruction personnel in operation and maintenance of the equipment, on the dates requested by the Owner.

OEM PPS-19 Generators 7 WTC March 20, 1998

NYC-WTC_000166894

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000166894Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Electrical proposal, ADCO Electrical Corp., May 1998 · Box 7DCAS

NYC-WTC_000172686

Revised electrical work proposal from ADCO Electrical Corporation for the Mayor's Office of Emergency Management on the 26th floor at 7 World Trade Center in May 1998.

2 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.881

machine-extracted · confidence unavailable · Check page ↗
HVAC specification supplement, unknown date · Box 7DCAS

NYC-WTC_000173223

Supplement to HVAC specifications detailing discharge plenum construction standards for emergency generators at the Mayor's Office of Emergency Management.

1 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.879

machine-extracted · confidence unavailable · Check page ↗

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →