NYC 9/11 Public Portal Document
1 1.04 RECORD DRAWINGS
Prepare as-built record drawings as follows:
A. On tracing cloth in ink. or on mylar.
B. Include all portions of permanent construction specified in
this Section.
C. Use cloth 36" x 14" with 1/2" margins and scale 1" = 30'.
D. Show Contractor, Port Authority Contract Number, all pipe
lengths, valves, fittings, connections, dimensions and hori
zontal and vertical locations and all other data necessary
to permit determination of exact location and physical char
acteristics of all parts of the piping, valves, connections
and appurtenances.
E. A sample drawing may be viewed in the office of the Engin
eer .
1.05 SUBMITTALS
Submit Shop Drawings for all rodding and bandings.
PART 2 - PRODUCTS
2.01 DUCTILE IRON WATER PIPE
A. Type II, Grade C, thickness class 56, cement lined, bitumi
nous coated inside and out conforming to the requirements of
Federal Specification WW-P-421D.
B. Type III, meeting all requirements of 2.01 A.
2.02 FITTINGS FOR DUCTILE IRON PIPE
Type II or Type III and/or as shown on the Contract Drawing for
pressure rating of 250 psi, ductile iron, cement lined, bitumi
nous coated inside and out conforming to the requirements of
ANSI A21.10 (AWWA CllO). Lining and coating shall be in accor
dance with those specified for the pipe.
2.03 BITUMASTIC PAINT
No. 50 as manufactured by the Koppers Company or No. CA-50 as
manufactured by the Barrett Division of the Allied Chemical and
Dye Corporation or approved equal.