( 2.04 CEMENT MORTAR LINING FOR DUCTILE IRON PIPE
Shall conform to the requirements of ANSI A21.4 except that the
thickness of the lining shall be twice that specified in Section
4-10.1.
PART 3 - EXECUTION
3.01 EXCAVATION AND BACKFILL
A. Verify that excavation and backfill is performed in accord
ance with requirements of Section entitled "Excavation,
Backfill and Pavement Restoration" and so as to provide a
minimum of 4' cover over pipe unless otherwise shown on
Contract Drawings.
B. Before placing pipe in trench finish bottom of trench by
hand and compact so as to support pipe for its entire
length.
C. If water enters trench, remove it and suspend operations
until a method for preventing the accumulation of water in
the bottom of trench is approved by the Engineer, and is
effee ted.
f
D. Where ground water exists in trench at or above the invert
level such that in the opinion of the Engineer, laying of
pipe as required by B and C above is impractical, use of
blocking in laying of pipe will be permitted.
3.02 PIPE RESTRAINT
TYPE II AND TYPE III - PIPE RODDING AND BANDING
A. Rod and band joints where and in accordance with details
shown on Contract Drawings.
B. Install bands with full bearing against pipe bells.
C. Do not install bands which depend upon friction between pipe
or fitting and band.
D. Where no bell is available at a joint requiring rodding, ex
tend rods to next bell, and where such rods are in excess of
6' long, provide intermediate supporting bands at intervals
of 6' or less.
/5'