Encapsulant coatings shall be for specific use in ventilation systems and applied per manufacturer's instructions including safety instructions. Encapsulant coatings shall be applied directly to the interior porous surfaces of AC/ventilation system components by hand brushing, rolling, or troweling, or via spray system, with a maximum distance of 24" from the spray discharge tip to the surface being treated. Encapsulant coatings may not be fogged into the system. A continuous film thickness should be achieved in treated areas, as per manufacturer's instructions. Encapsulants shall be water-based, with low VOC (volatile organic compound) emissions, and meet NFPA smoke development and flame spread requirements for ventilation system products. Encapsulant coatings shall be applied in accordance with applicable federal, state, or local regulations regarding the use of such products and MSDS copies for any encapsulant products used in the AC/ventilation system shall be available on-site.
Areas of damaged interior AC/ventilation system fan unit or duct insulation that is abraded or delaminated such that application of an encapsulant coating would be inappropriate as determined by the NADCA-certified ASCS should be removed in consultation with building management. Replacement of such insulation with an appropriate material shall be the responsibility of building management.
Procedures
1. Identify the system to be cleaned including outside air intake, fan unit, supply ducts and return ducts if appropriate.
2. Determine how the system will be segregated for cleaning; typically the fan unit will be cleaned separately from the ductwork unless the ductwork consists of very short runs on the same floor. As a general procedure, cleaning work should follow the ventilation system air flow. Cleaning should start at the outside air intake or return ducts, proceed to the air handling unit, and then proceed through the supply side of the air distribution system to the supply air diffusers.
3. Lock out and tag out the fan unit. Note that the NYFD needs to be contacted to determine permitting procedures if there are in-duct smoke detectors as these need to be disabled for duct cleaning.
4. Attach a local capture, HEPA filtered, Air Filtration Device (AFD) or vacuum collection system to the lowest opening of a riser or the fiirthest point of a horizontal duct, to place the system under negative pressure. Sufficient negative pressure shall be maintained to prevent the dispersion of dust outside of the duct. Isolation/zone pillows shall be used as necessary to isolate sections of the system, so that sufficient negative pressure is maintained in each work zone.
5. Exhaust the AFD or vacuum collection system to the outdoors through a window. If no window is available, a stairwell may be appropriate. Alternately, two AFD’s or vacuum collection systems may be connected in series so that a second unit filters the exhaust air from the first. Another method of ensuring that air contaminants do not leak through an air cleaning device is through in-place leak testing of the filtration component using DOP testing.
6. Cover all open supply air grilles, supply diffusers, and return air grilles located in the affected ductwork using fire-retardant polyethylene sheeting or bags and duct tape.
NYC-WTC_000162726
OCR can misread numbers and units. Confirm readings against the page image before using them.
Related records
Browse subjects →Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
Same-box records
6 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000162731
EPA submits detailed technical questions and comments on proposed HVAC cleaning procedures for WTC buildings.
5 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.960
machine-extracted · confidence unavailable · Check page ↗Filed elsewhere
NYC-WTC_000140014
Technical specifications for the application of encapsulant coatings on ventilation system components, including safety and material requirements.
1 shared non-person entities · 1 shared topics · similarity 0.954
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140027
Technical guidance on maintaining air velocity and negative pressure during duct cleaning, HEPA device specifications, and dust containment methods.
3 shared non-person entities · 1 shared topics · similarity 0.951
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140011
Technical comments regarding air velocity requirements and equipment specifications for duct cleaning operations.
3 shared non-person entities · 1 shared topics · similarity 0.947
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140013
Technical specifications for the application of encapsulant coatings on ventilation system components.
4 shared non-person entities · 1 shared topics · similarity 0.947
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140028
Detailed procedures for isolating ventilation zones, sealing exhaust grilles, cleaning roof-mounted components, and managing contaminated waste.
1 shared non-person entities · 1 shared topics · similarity 0.946
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140026
Draft cleaning protocol specifying isolation techniques, vacuum collection methods, HEPA equipment use, and contamination control procedures for ventilation ducts.
4 shared non-person entities · 1 shared topics · similarity 0.944
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140511
Draft document outlining regulations and assistance programs for residential cleaning following the World Trade Center collapse.
4 shared non-person entities · 1 shared topics · similarity 0.942
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140517
Departmental comments and requests for clarification regarding cleaning triggers, clearance levels, and supervision requirements.
4 shared non-person entities · 1 shared topics · similarity 0.939
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140603
Contract establishing requirements for third-party asbestos monitoring and air sampling in residential buildings.
4 shared non-person entities · 1 shared topics · similarity 0.939
machine-extracted · confidence unavailable · Check page ↗More like this page
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Page similarity is temporarily unavailable or this page has no indexed vector.
Others also read
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000162712
Official notice instructing staff to preserve scanned World Trade Center documents as potential evidence in future legal actions.
Filed in the same folder
NYC-WTC_000162713
Official notice instructing staff not to dispose of original World Trade Center documents as they are required for legal proceedings.
Filed in the same folder
NYC-WTC_000162729
DEP submits OSHA compliance justification document for review regarding worker safety in WTC cleanup procedures.
Filed in the same folder
NYC-WTC_000162731
EPA submits detailed technical questions and comments on proposed HVAC cleaning procedures for WTC buildings.
Filed in the same folder
Filed in the same folder