or AFDs may be connected in series so that a second unit filters the exhaust air from the
first. Another method of verifying that air contaminants do not leak through an air
cleaning device is through in-place leak-testing of the filtration component using POP
testing.
6. Install one layer of 6 mil poly over all bathroom and kitchen exhaust grilles and secure in
place with painters tape.
i^Insert and inflate isolation/zone pillows, as necessary to isolate system, so that floors
beyond the cleaning scope area outside the work zoner, and to maintain sufficient
negative pressure in the section of the ventilation system being cleaned.
6r8.Remove the mushroom or other fan type housing or weather cap assembly from the roof j
mounting.
^^Disassemble and clean the mushroom assembly using HEPA vacuums with brush |
attachments and wet methods, as necessary to remove dust (any electrical equipment will
not be cleaned with wet methods).
10. Clean the main riser from the roof or top most floor of the cleaning zone, using a
combination of techniques including whips, brushes, and compressed air (note;
compressed air may be used only if the system is sufSciently isolated and vacuum
collection equipment is used to maintain a duct velocity of approximately 3000 feet per
minute to capture and transport dislodged material). The riser should be cleaned prior to
cleaning the branch ducts.
11. Reinstall the mushroom, other type housing or weather cap once the riser or top zone is
cleaned.
12. For accessible branch ducts (typically 6 or less in length from access point): One by
one, place an approximately 6’ x 6’ drop cloth of polyethylene sheeting on the surfaces
below each bathroom and kitchen exhaust vent. Remove and clean each bathroom and
kitchen exhaust grille inside the affected apartment. Clean all branch ducts from inside
the apartment bathrooms and kitchens, using HEPA vacuums with brush attachments and
wet methods. After cleaning, reinstall the bathroom or kitchen exhaust grille and cover
again with polyethylene sheeting secured with painter’s tape to help maintain negative
pressure within the exhaust ventilation system before moving on to the next grille. Roll
up the polyethylene sheeting protecting the surfaces below the exhaust vent and place in a
6 mil polyethylene bag for disposal.
8.RemGve and clean all bathroom-aad kitchen exhaust grills inside affected apartments.
Q.Clean- all branch ducts from inside the apartment bathrooms and kitchens, using HEPA
vacumns with brush attachments and wet methods.
P 13. For inaccessible branch ducts (typically 6’ or greater in length from access point): prior
» to inserting mechanical cleaning devices into the access point, construct a “cube” or
“cocoon” to contain the access point. Remove and clean the grille. Clean the branch
duct using a combination of whips, brushes, and compressed air (note: compressed air