Receiving report for HVAC consulting services, March-April 2003

Machine-extracted title · confidence 94%

City receiving report acknowledging delivery of HVAC consulting services for WTC from TAMS Consultants Inc.

NYC-WTC_000135765–000135950
Page image
Scanned page image, NYC-WTC_000135784
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

under negative pressure using a HEPA-filtered air filtration device is sufficient. The footprint of the containment should be large enough to accommodate a ladder or scaffolding if needed.

8. If there is an outside air intake, clean the intake louvers by damp wiping. If there is an outside air duct and it is accessible, clean the interior surfaces using HEPA vacuums with brush attachments and wet methods. If access to the outside air duct is limited, clean it using a combination of whips (whips only used in ducts without interior insulation), brushes (use soft brushes if ducts have interior insulation), and compressed air (note: compressed air may be used only if the system is sufficiently isolated and vacuum collection equipment is used to maintain a duct velocity of approximately 3000 feet per minute). Note that vertical risers may be treated similarly to the procedures identified for exhaust ducts.

9. Clean the air intake louvers and filter racks at the return air sides of the AC/ventilation units by damp wiping.

10. Clean all parts of the A/C or ventilation fan unit exposed to the air stream including thermal coils, the blower assembly and housing, and all other components using HEPA vacuum brush attachments and minimal wet methods. Electric coils and components shall be cleaned using dry methods. When wet cleaning thermal coils, apply manufacturer-approved cleaning solution to the coils using low pressure methods (i.e., airless sprayer, hand operated pump).

11. Clean all supply mains and branch ducts starting at the furthest point from the AFD or vacuum col]ecticn device. If the ducts are accessible (typically 6' or less in length from access point) they may be cleaned using HEPA vacuums with brush attachments and wet methods. If access to the ducts is limited (typically 6' or more in length from access point), clean them using a combination of whips (whips only used in ducts without interior insulation), brushes (use soft brushes if ducts have interior insulation), and compressed air (note: compressed air may be used only if the system is sufficiently isolated and vacuum collection equipment is used to maintain a duct velocity of approximately 3000 feet per minute).

Use isolation/zone pillows as necessary to isolate sections of the system, so that sufficient negative pressure is maintained in each work zone and to prevent re-contamination of cleaned sections.

12. Apply encapsulant to any exposed porous insulation in the AC/ventilation system fan unit or ducts.

13. Protect the floor underneath the supply grilles/diffusers or return air grilles using 6 mil polyethylene sheeting. Remove the polyethylene barriers covering the supply air diffusers/grilles and return grilles, while the duct is still under negative pressure.

14. Remove supply air grilles and diffusers to a central location for cleaning. Clean using Simple Green or a similar environmentally safe product. Use bags if necessary when removing the grilles and/or diffusers to prevent dust or debris from being released. Reinstall supply grilles/diffusers and return air grilles after cleaning.

13. Air filters within the AC/ventilation system shall removed and disposed of. It shall be the responsibility of building management to provide replacement filters.

NYC-WTC 000135784

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000135784Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000117345 · Box DEP Box 46

January 30, 2003 letter from Athenica Environmental Services regarding HVAC and environmental inspections at 250 South End Avenue.

Similar indexed content

Compare copies and versions →