systems or AFD’s may be connected in series so that a second unit filters the exhaust air
from the first. Another method of verifying that air contaminants do not leak through an
air cleaning device is through in-place leak testing of the filtration component using DOP
testing.
6. Install one layer of 6 mil poly over all bathroom and kitchen exhaust grilles and secure in
place with painters tape.
7. Insert and inflate isolation/zone pillows, as necessary to isolate system, so that floors
beyond the cleaning scope area outside the work zone, and to maintain sufficient negative
pressure in the section of the ventilation system being cleaned.
8. Remove the mushroom or other fan type housing or weather cap assembly from the roof
mounting.
9. Disassemble and clean the mushroom, other fan type housing or weather cap assembly
using HEPA vacuums with brush attachments and wet methods, as necessary to remove
dust (any electrical equipment will not be cleaned with wet methods).
10. Clean the main riser from the roof or top most floor of the cleaning zone, using a
combination of techniques including whips, brushes, and compressed air (note:
compressed air may be used only if the system is sufficiently isolated and vacuum
collection equipment is used to maintain a duct velocity of approximately 3000 feet per
minute to capture and transport dislodged material). Clean the riser prior to cleaning the
associated branch ducts.
11. Reinstall the mushroom, other fan type housing or weather cap assembly once the riser or
top zone is cleaned.
12. For accessible branch ducts (typically 6’ or less in length from access point): One by
one, place an approximately 6’ x 6’ drop cloth of 6 mil polyethylene sheeting on the
surfaces below each bathroom and kitchen exhaust grille. Check to ensure that the face
velocity at the grille opening is 500 feet per minute or greater. Remove and clean each
bathroom and kitchen exhaust grille inside the affected apartment. Clean all branch ducts
from inside the apartment bathrooms and kitchens, using HEPA vacuums with brush
attachments and wet methods. After cleaning, reinstall the bathroom or kitchen exhaust
grille and cover again with polyethylene sheeting secured with painter’s tape to help
maintain negative pressure within the exhaust ventilation system before moving on to the
next grille. Roll up the polyethylene sheeting protecting die surfaces below the exhaust
vent and place in a 6 mil polyethylene bag for disposal as asbestos-containing waste.
13. For inaccessible branch ducts (typically 6’ or greater in length from access point): prior
to inserting mechanical cleaning devices into the access point, construct a temporary
containment (see General item 2) to contain the access point. Remove and clean the
grille. Clean the branch duct using a combination of whips, brushes, and compressed air
(note: compressed air may be used only if the system is sufficiently isolated and vacuum
collection equipment is used to maintain a duct velocity of approximately 3' feet per
minute).
Use isolation/zone pillows as necessary to isolate sections of the system, so that sufficient
negative pressure is maintained in each work zone and to prevent re-contamination of
cleaned sections.