NYC 9/11 Public Portal Document
After cleaning, reinstall the bathroom or kitchen exhaust grille and cover again with
polyethylene sheeting secured with painter’s tape to help maintain negative pressure
within the exhaust ventilation system before moving on to the next grille. HEPA vacuum
or wet-wipe interior surfaces of the temporary containment prior to dismantling or
moving to another location. Place all waste in 6 mil polyethylene bags for disposal as
asbestos-containing waste.
14. Disengage the local capture system and relocate to another section of the riser or to
another riser.
15. Ensure that the occupant space is free of any debris associated with the duct cleaning
process. Use HEPA vacuums and/or wet wiping to clean the space, as needed. Place
waste and debris into 6 mil polyethylene bags for disposal as asbestos-containing waste.
16. Perform all duct cleaning work in accordance with local, state and federal regulations.
17. All work will be accomplished by a DEP certified Asbestos Handlers.
18. All work will be supervised by a DEP certified Asbestos Handler Supervisor.
19. Workers will utilize /aface APR’s equipped with P-100 filters, eye protection and full
body coveralls during the cleaning process.
NYC-WTC_000162724