NYC 9/11 Public Portal Document
WTC Indoor Dust Cleaning Program
Draft Exhaust System Cleaning Procedures
General
1. It is necessary to ensure that sufficient air velocity and/or negative pressure is maintained in
the duct during cleaning, to prevent the dispersion of dust outside of the duct and to ensure
that debris dislodged by mechanical cleaning devices is transported to a collection device. A
HEPA filtered Air Filtration Device (AFD), which is typically used for asbestos abatement
and is not designed for use within exhaust systems, may not provide sufficient velocity for
this purpose, although AFD’s may be acceptable in some cases, e.g., in smaller systems with
light dust loading. Vacuum collection systems are employed by duct cleaning contractors for
this purpose.
The AFD or vacuum collection equipment shall be adequate to collect all dust and debris
released by the cleaning process and shall be attached to the existing ductwork with air-tight
connections and located to attain maximum collection efficiency.
2. Provisions must be made to prevent the release of dust or debris at access points that are
disturbed by the cleaning activities. If the branch ducts are accessible (typically 6’ or less in
length from access point) it is not necessary to construct a temporary containment at the
access point provided that a) they may be cleaned using HEPA vacuums with brush
attachments and wet methods and b) negative pressure within the system is sufficient to
provide a face velocity at the grille opening of 500 feet per minute. For larger branches that
require the use of mechanical devices such as whips, brushes, and compressed air, or where it
is not possible to establish a face velocity at the grille opening of 500 feet per minute,
construct a temporary containment (e.g., a “cube” or “cocoon” with flapped entrance) at the
access point to provide protection against the release of dust.
3. It is recommended that air filtration devices and vacuum collection equipment be exhausted
to the outdoors unless special measures are taken to control the leakage of air contaminants
from the exhaust of such equipment.
Procedures
1. Identify the system to be cleaned including exhaust fan (e.g., “mushroom” fans), number
and location of risers, and apartments or common spaces affected.
2. Determine how many floors on a riser will be cleaned as part of one continuous cleaning
(5-10 floors).
3. Lock out and tag out the exhaust fan.
4. Attach a local capture, HEPA filtered, vacuum collection system or AFD to the lowest
opening of the riser to place the system under negative pressure (i.e., exhaust vent in an
apartment at the bottom of the riser being cleaned). Polyethylene sheeting should be used
to protect the floor underneath the vacuum collection equipment.
5. Exhaust the vacuum collection system or AFD to the outdoors through a window. If no
window is available, a stairwell may be appropriate. Alternately, two vacuum collection
NYC-WTC_000162722