WTC Indoor Dust Cleaning Program Exhaust System Y Cleaning Procedures

General

1. It is necessary to ensure that sufficient air velocity and/or negative pressure is maintained in the duct during cleaning, to prevent the dispersion of dust outside of the duct and to ensure that debris dislodged by mechanical cleaning devices is transported to a collection device. A HEPA filtered vacuum collection device shall be used to create negative pressure within the ductwork to be cleaned. The AFD or vacuum collection equipment shall be adequate to collect all dust and debris released by the cleaning process and shall be attached to the existing ductwork with air-tight connections and located to attain maximum collection efficiency. Smoke tubes or other equivalent methods will be used to verify that sufficient air velocity is maintained during cleaning.

2. Provisions must be made to prevent the release of dust or debris at access points that are disturbed by the cleaning activities. If the branch ducts are accessible (typically 6' or less in length from access point) it is not necessary to construct a temporary containment at the access point provided that a) they may be cleaned using HEPA vacuums with brush attachments and wet methods and b) negative pressure within the system is sufficient to provide a face velocity at the grille opening of 500 feet per minute. For larger branches (typically 6' or greater in length from access point) that require the use of mechanical devices such as whips, brushes, and compressed air, or where it is not possible to establish a face velocity at the grille opening of 500 feet per minute, construct a temporary containment (e.g., a "cube" or "cocoon" with flapped entrance) at the access point to provide protection against the release of dust. Containment is not required for air handling units located outdoors unless located near active air intakes. Smoke tubes or other equivalent methods will be used periodically throughout the cleaning process and during activities that create the greatest potential for worker exposure to verify that sufficient air velocity is maintained.

3. It is recommended that air filtration devices and vacuum collection equipment be exhausted to the outdoors unless special measures are taken to control the leakage of air contaminants from the exhaust of such equipment (see Procedures item 7).

Procedures

1. Identify the system to be cleaned including exhaust fan (e.g., "mushroom" fans), number and location of risers, and apartments or common spaces affected.

2. Determine how many floors on a riser will be cleaned as part of one continuous cleaning (5-10 floors).

3. Lock out and tag out the exhaust fan.

4. Attach a local capture, HEPA filtered, vacuum collection system to the riser to place the system under negative pressure. Polyethylene sheeting should be used to protect the floor underneath the vacuum collection equipment if located indoors.

NYC-WTC 000135779

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000135779Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000117345 · Box DEP Box 46

January 30, 2003 letter from Athenica Environmental Services regarding HVAC and environmental inspections at 250 South End Avenue.

Similar indexed content

Compare copies and versions →