WTC Indoor Dust Cleaning Program Exhaust System Cleaning Procedures General
1. It is necessary to ensure that sufficient air velocity and/or negative pressure is maintained in the duct during cleaning, to prevent the dispersion of dust outside of the duct and to ensure that debris dislodged by mechanical cleaning devices is transported to a collection device. A HEPA filtered vacuum collection device shall be used to depressurize the ductwork to be cleaned. The AFD or vacuum collection equipment shall be adequate to collect all dust and debris released by the cleaning process and shall be attached to the existing ductwork with air-tight connections and located to attain maximum collection efficiency.
2. Provisions must be made to prevent the release of dust or debris at access points that are disturbed by the cleaning activities. If the branch ducts are accessible (typically 6’ or less in length from access point) it is not necessary to construct a temporary containment at the access point provided that a) they may be cleaned using HEPA vacuums with brush attachments and wet methods and b) negative pressure within the system is sufficient to provide a face velocity at the grille opening of 500 feet per minute. For larger branches (typically 6’ or greater in length from access point) that require the use of mechanical devices such as whips, brushes, and compressed air, or where it is not possible to establish a face velocity at the grille opening of 500 feet per minute, construct a temporary containment (e.g., a “cube” or “cocoon” with flapped entrance) at the access point to provide protection against the release of dust. Containment is not required for air handling units located outdoors unless located near active air intakes.
3. It is recommended that air filtration devices and vacuum collection equipment be exhausted to the outdoors unless special measures are taken to control the leakage of air contaminants from the exhaust of such equipment (see Procedures item 7).
Procedures
1. Identify the system to be cleaned including exhaust fan (e.g., “mushroom” fans), number and location of risers, and apartments or common spaces affected.
2. Determine how many floors on a riser will be cleaned as part of one continuous cleaning (5-10 floors).
3. Lock out and tag out the exhaust fan.
4. Attach a local capture, HEPA filtered, vacuum collection system to the riser to place the system under negative pressure. Polyethylene sheeting should be used to protect the floor underneath the vacuum collection equipment if located indoors.
5. Exhaust the vacuum collection system or AFD to the outdoors. If no window is available, a stairwell may be appropriate. Alternately, two vacuum collection systems or AFD’s may be connected in series so that a second unit filters the exhaust air from the first. Alternately, the cleaning contractor can have the collection equipment leak tested in-place by an independent third party to ensure that contaminants do not leak through the air cleaning device.
NYC-WTC_000162751
OCR can misread numbers and units. Confirm readings against the page image before using them.
Related records
Browse subjects →Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
Same-box records
6 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.995
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000162731
EPA submits detailed technical questions and comments on proposed HVAC cleaning procedures for WTC buildings.
5 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.960
machine-extracted · confidence unavailable · Check page ↗Filed elsewhere
NYC-WTC_000140014
Technical specifications for the application of encapsulant coatings on ventilation system components, including safety and material requirements.
1 shared non-person entities · 1 shared topics · similarity 0.953
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140013
Technical specifications for the application of encapsulant coatings on ventilation system components.
4 shared non-person entities · 1 shared topics · similarity 0.952
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140027
Technical guidance on maintaining air velocity and negative pressure during duct cleaning, HEPA device specifications, and dust containment methods.
3 shared non-person entities · 1 shared topics · similarity 0.950
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140026
Draft cleaning protocol specifying isolation techniques, vacuum collection methods, HEPA equipment use, and contamination control procedures for ventilation ducts.
4 shared non-person entities · 1 shared topics · similarity 0.949
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140511
Draft document outlining regulations and assistance programs for residential cleaning following the World Trade Center collapse.
4 shared non-person entities · 1 shared topics · similarity 0.949
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140517
Departmental comments and requests for clarification regarding cleaning triggers, clearance levels, and supervision requirements.
4 shared non-person entities · 1 shared topics · similarity 0.949
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140603
Contract establishing requirements for third-party asbestos monitoring and air sampling in residential buildings.
4 shared non-person entities · 1 shared topics · similarity 0.946
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000097177
Permit application requesting licensed asbestos contractors to clean debris and dust from the interior of 125 Cedar Street.
4 shared non-person entities · 1 shared topics · similarity 0.944
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000165014
Memo from EPA to multiple NYC, state, and federal agencies coordinating WTC environmental response activities and information sharing.
3 shared non-person entities · 1 shared topics · similarity 0.944
machine-extracted · confidence unavailable · Check page ↗More like this page
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Page similarity is temporarily unavailable or this page has no indexed vector.
Others also read
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000162712
Official notice instructing staff to preserve scanned World Trade Center documents as potential evidence in future legal actions.
Filed in the same folder
NYC-WTC_000162713
Official notice instructing staff not to dispose of original World Trade Center documents as they are required for legal proceedings.
Filed in the same folder
Filed in the same folder
NYC-WTC_000162729
DEP submits OSHA compliance justification document for review regarding worker safety in WTC cleanup procedures.
Filed in the same folder
NYC-WTC_000162731
EPA submits detailed technical questions and comments on proposed HVAC cleaning procedures for WTC buildings.
Filed in the same folder