7. Place the air handling units and their components under containment prior to beginning work. A temporary Zip-wall containment of 6-mil, fire retardant polyethylene sheeting extending from the floor to the ceiling deck, and maintained under negative pressure using a HEPA-filtered air filtration device is sufficient. The footprint of the containment should be large enough to accommodate a ladder or scaffolding if needed.
8. If there is an outside air intake, clean the intake louvers by damp wiping. If there is an outside air duct and it is accessible, clean the interior surfaces using HEPA vacuums with brush attachments and wet methods. If access to the outside air duct is limited, clean it using a combination of whips (whips only used in ducts without interior insulation), brushes (use soft brushes if ducts have interior insulation), and compressed air (note: compressed air may be used only if the system is sufficiently isolated and vacuum collection equipment is used to maintain a duct velocity of approximately 3 feet per minute). Note that vertical risers may be treated similarly to the procedures identified for exhaust ducts.
9. Clean the air intake louvers and filter racks at the return air sides of the AC/ventilation units by damp wiping.
10. Clean all parts of the A/C or ventilation fan unit exposed to the air stream including thermal coils, the blower assembly and housing, and all other components using HEPA vacuum brush attachments and minimal wet methods. Electric coils and components shall be cleaned using dry methods. When wet cleaning thermal coils, apply manufacturer-approved cleaning solution to the coils using low pressure methods (i.e., airless sprayer, hand operated pump).
11. Clean all supply mains and branch ducts in the direction of air flow, starting from the furthest point from the AFD or vacuum collection device. If the ducts are accessible (typically 6’ or less in length from access point) they may be cleaned using HEPA vacuums with brush attachments and wet methods. If access to the ducts is limited, clean them using a combination of whips (whips only used in ducts without interior insulation), brushes (use soft brushes if ducts have interior insulation), and compressed air (note: compressed air may be used only if the system is sufficiently isolated and vacuum collection equipment is used to maintain a duct velocity of approximately 3’S3 feet per minute).
Use isolation/zone pillows as necessary to isolate sections of the system, so that sufficient negative pressure is maintained in each work zone and to prevent re-contamination of cleaned sections.
12. Apply encapsulant to any exposed porous insulation in the AC/ventilation system fan unit or ducts.
13. Protect the floor underneath the supply grilles/diffusers or return air grilles using 6 mil polyethylene sheeting. Remove the polyethylene barriers covering the supply air diffusers/grilles and return grilles, while the duct is still under negative pressure.
14. Remove supply air grilles and diffusers to a central location for cleaning. Clean using Simple Green or a similar environmentally safe product. Use bags if necessary when removing the grilles and/or diffusers to prevent dust or debris from being released. Reinstall supply grilles/diffusers and return air grilles after cleaning.
NYC-WTC_000162727
OCR can misread numbers and units. Confirm readings against the page image before using them.
Related records
Browse subjects →Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
Same-box records
6 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.994
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000162731
EPA submits detailed technical questions and comments on proposed HVAC cleaning procedures for WTC buildings.
5 shared non-person entities · 1 shared topics · Same agency, volume and box · similarity 0.960
machine-extracted · confidence unavailable · Check page ↗Filed elsewhere
NYC-WTC_000140014
Technical specifications for the application of encapsulant coatings on ventilation system components, including safety and material requirements.
1 shared non-person entities · 1 shared topics · similarity 0.954
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140027
Technical guidance on maintaining air velocity and negative pressure during duct cleaning, HEPA device specifications, and dust containment methods.
3 shared non-person entities · 1 shared topics · similarity 0.951
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140011
Technical comments regarding air velocity requirements and equipment specifications for duct cleaning operations.
3 shared non-person entities · 1 shared topics · similarity 0.947
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140013
Technical specifications for the application of encapsulant coatings on ventilation system components.
4 shared non-person entities · 1 shared topics · similarity 0.947
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140028
Detailed procedures for isolating ventilation zones, sealing exhaust grilles, cleaning roof-mounted components, and managing contaminated waste.
1 shared non-person entities · 1 shared topics · similarity 0.946
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140026
Draft cleaning protocol specifying isolation techniques, vacuum collection methods, HEPA equipment use, and contamination control procedures for ventilation ducts.
4 shared non-person entities · 1 shared topics · similarity 0.944
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140511
Draft document outlining regulations and assistance programs for residential cleaning following the World Trade Center collapse.
4 shared non-person entities · 1 shared topics · similarity 0.942
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140517
Departmental comments and requests for clarification regarding cleaning triggers, clearance levels, and supervision requirements.
4 shared non-person entities · 1 shared topics · similarity 0.939
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000140603
Contract establishing requirements for third-party asbestos monitoring and air sampling in residential buildings.
4 shared non-person entities · 1 shared topics · similarity 0.939
machine-extracted · confidence unavailable · Check page ↗More like this page
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Page similarity is temporarily unavailable or this page has no indexed vector.
Others also read
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000162712
Official notice instructing staff to preserve scanned World Trade Center documents as potential evidence in future legal actions.
Filed in the same folder
NYC-WTC_000162713
Official notice instructing staff not to dispose of original World Trade Center documents as they are required for legal proceedings.
Filed in the same folder
NYC-WTC_000162729
DEP submits OSHA compliance justification document for review regarding worker safety in WTC cleanup procedures.
Filed in the same folder
NYC-WTC_000162731
EPA submits detailed technical questions and comments on proposed HVAC cleaning procedures for WTC buildings.
Filed in the same folder
Filed in the same folder